Fire-Lite IPDACT Installation Manual User Manual
Page 25
IPDACT Module – Installationg and cabling
III-22
Doc.Dm373-I
Rev. 2.0
The IPDACT wiring is limited in power. Therefore all the wiring
between the IPDACT box and the panel can be enclosed in the
same metal conduit.
III - 2.1.2. Installation instructions
The following instructions are specific to wiring between the IPDACT and the
Firelite MS-9200UD panel. For any other panel, please consult the
manufacturers’ documentation and instructions.
•
Before carrying out any type of operation on the wiring, make sure you
have disconnected all power sources.
•
In these installations the IPDACT must be integrated in its box. Connect
the IPDACT box ground to the same ground point where you have
connected the panel ground. This is to prevent current traveling through
grounded circuits. Grounding is essential to avoid unwanted electrostatics
discharges.
Figure 19. Earth ground for the IPDACT and panel boxes.
•
Connect the IPDACT power inputs to the panel TB1 connector,
terminals 1 and 2. These terminals can be configured as resettable
or non-resettable power. The latter implies an uninterrupted power
source from the panel and is the one we recommend.
The IPDACT GND terminal is not connected to the box earth ground.