Fire-Lite IPDACT Installation Manual User Manual
Page 36

IPDACT Module - Configuration
IV-33
Doc.Dm373-I
Rev. 2.0
Remote configuration request
This permits you to prompt the Teldat VisorALARM for the complete configuration 
required by the IPDACT in order to function. This register does not require you to 
configure any parameters and is limited to simply execute a request. In order to 
do this, you require the installer password. 
The configuration the IPDACT receives has been configured in the VisorALARM 
through a profile. The parameters common to a set of IPDACTs are in the said 
profile. 
The register mechanism permits you to quickly configure a set of IPDACTs with 
common parameters. Only those parameters which uniquely identify an IPDACT 
must be configured by the installer: account number, local IP parameters, output 
switch and actions to take should the PSTN fail. 
The register is composed of one field with up to 16 digits. By default this register 
is not configured with a value. Should you enter a value, it is not maintained 
between requests. For further information, please see section IV-2.1.3. 
IPDACT Reset
Permits you to reset the IPDACT so that some parameters have validity. So that 
the operation is effective you need to provide the access password for the 
console. 
The register is made up of a single field, corresponding to the access password. If 
the password is valid, the device will reset; should this be incorrect an error tone 
will be emitted followed by the console dialing tone. This register does not store 
any data in the IPDACT configuration. 
IPDACT account number
Account number identifying the IPDACT to the IP Visor Alarm receiver and the 
security company’s automation software. In order to simplify the identification 
process, we recommend that the last four figures in this parameter coincide with 
the account number assigned to the control panel to which this is designated. 
The register is made up of one 6-digit field. The default value is 000000.
Teldat VisorALARM IP address
IP address for the IP VisorALARM receiver which receives both the monitoring 
traffic as well as the traffic corresponding to the alarms generated by the control 
panel. 
The register is made up of 4 fields corresponding to the 4 numbers in the IP 
address; this admits values between 0 and 255. Each number has a verification 
digit. This contains the following value by default: 
000
000
000
000