Fire-Lite IPDACT Installation Manual User Manual
Page 35
IPDACT Module - Configuration
IV-32
Doc.Dm373-I
Rev. 2.0
IV - 3.1.1. Default Configuration
Through a short circuit in the IPDACT P2 jumper during the start up process,
you can configure the IPDACT with the factory settings. This configuration is
displayed in the previous table.
The process for this is as follows: 1) switch off the IPDACT, 2) short circuit
the P2 jumper, 3) switch on the device, 4) maintain the P2 short circuited
during the first burst from LEDs A, B, C and D (they light up and switch off
consecutively) and open it half way through the second burst. If the process
has executed successfully, the IPDACT will display a third burst indicating the
default configuration has been activated.
IV - 3.1.2. Register description
IPDACT IP address and mask
IP address and mask associated to the IPDACT in order to operate in the client’s
local network. From IPDACT software release 2.0 onwards, this parameter is only
necessary in cases where you do not have a DHCP server or as a backup
configuration in cases where the said DHCP server is down.
The register is made up of 8 fields; both the IP address as well as the mask is
composed of 4 numbers between 0 and 255. Each number has a verification digit.
This contains the following
value by default:
IPDACT access Gateway
IP address associated to the access gateway in the client local network. This
gateway gathers all the traffic from the IPDACT and ensures that it reaches the
next hop to the Teldat VisorALARM. From IPDACT software release 2.0 onwards,
this parameter is only necessary in cases where you do not have a DHCP server
or as a backup configuration in cases where the said DHCP server is down.
The register is made up of 4 fields corresponding to the 4 numbers in the IP
address; this admits values between 0 and 255. Each number has a verification
digit. This contains the following value by default:
Access password for the console
Access password for the telephonic console which prevents unauthorized access.
This is also used to verify some operations. This must be entered twice in order to
validate it.
The register is made up of one field with up to 16 digits. The default value is
24680.
The password field cannot be left empty.
192
168
000
100
255
255
255
000
192
168
000
200