Appendix a: programming sheets, A.1 digital communicator options program sheets, A.1: digital communicator options program sheets – Fire-Lite 411UDAC Fire Alarm Communicator User Manual
Page 66

66
411UDAC Manual — P/N 51073:E 9/20/2013
Appendix A: Programming Sheets
A.1 Digital Communicator Options Program Sheets
To enter Programming Mode, press the MODE key, 7764, and then the [ENTER/STORE] key.
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number.
20
Primary Central Station Communication Format: Valid entries are 0 to 9 and A to F.
21
22
23
24
Primary Central Station Account Code: Valid entries are 0 to 9 and A to F.
25
26
27
28
Primary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).
29
Primary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to represent the end of number.
50
Secondary Central Station Communication Format: Valid entries are 0 to 9 and A to F.
51
52
53
54
Secondary Central Station Account Code: Valid entries are 0 - 9 and A - F.
55
56
57
58
Secondary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).
59
Secondary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.
60
AC Loss Reporting Delay. Enter '0' for no delay; '1' for 1 hours; '2' for 2 hours; '3' for 6 hours; '4' for 7 hours;
'5' for 8 hours; '6' for 9 hours; '7' for 10 hours; '8' for 11 hours; '9' for 12 hours; 'A' for 13 hours; 'B' for 14 hours; 'C' for
15 hours; 'D' for 16 hours; 'E' for 17 hours; 'F' for 18 hours.
61
Backup Reporting. Enter '0' to report to Secondary phone number as backup only; '1' to report to both Primary
and Secondary phone number for all reports/messages; '2' reports go to first available receiver.
62
Reserved for Future Use.
63
DACT Trouble Reminder. Enter '0' to disable; '1' to enable.
64
Operational Mode Selection. Enter '0' for stand-alone/communicator disabled; '1' for stand-alone/communi-
cator enabled; '2' for slave/communicator enabled; '3' for slave/communicator disabled. Default setting is '0'.
65
Input Channel 1 Function Selection. Enter '0' for fire alarm; '1' for pull station; '2' for normally open contact;
'3' for host panel trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for
waterflow nonsilenceable.
66
Input Channel 2 Function Selection. Enter '1' for pull station; '2' for normally open contact; '3' for host panel
trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsi-
lenceable.
67
Input Channel 3 Function Selection. Enter '0' for fire alarm; '1' for pull station; '2' for normally open contact;
'3' for host panel trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for
waterflow nonsilenceable.
68
Input Channel 4 Function Selection. Enter '1' for pull station; '2' for normally open contact; '3' for host panel
trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsi-
lenceable.
69
70
71
Input Channel 1 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.
Does not delay Input Channels programmed for fire functions.
72
73
74
Input Channel 2 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.
Does not delay Input Channels programmed for fire functions.
75
76
77
Input Channel 3 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay.
Does not delay Input Channels programmed for fire functions.