Ac loss reporting delay (60), Backup reporting (61), Reserved for future use (62) – Fire-Lite 411UDAC Fire Alarm Communicator User Manual
Page 45: Dact trouble reminder (63), Operational mode selection (64)
411UDAC Manual — P/N 51073:E 9/20/2013
45
Program Mode
Modes of Operation
Secondary Central Station Number Account Code (51 - 54)
The four locations at addresses 51 - 54 default to all '0's. Valid entries are 0 - 9 and A - F. The num-
ber of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 50,
enter three digits (one digit each in locations 51, 52 and 53 - location 54 is ignored). If program-
ming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into address 50, enter four digits (one each in locations 51, 52,
53 and 54).
Secondary Central Station Number 24 Hour Test Time (55 - 58)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1
takes up four locations, from addresses 55 - 58. The default is 00:00 (12:00 midnight). The limits
for each location are as follows (do not use values of A - F as entries):
55: enter 0, 1 or 2
56: enter 0 - 9
57: enter 0 - 5
58: enter 0 - 9
Secondary Central Station Number 24/12/8/6 Hour Test Time Interval (59)
The test report sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours. If the
message is to be sent every 24 hours, leave the factory default entry of '0'. If other test report times
are needed, enter 1 = 12 hour, 2 = 8 hour or 3 = 6 hour.
AC Loss Reporting Delay (60)
Enter a digit of 0 - 9 or A - F corresponding to the number of hours to be delayed in reporting the
loss of AC power. The factory default is '2' for 2 hours. The valid entries are '0' = no delay; '1' = 1
hours; '2' = 2 hours; '3' = 6 hours; '4' = 7 hours; '5' = 8 hours; '6' = 9 hours; '7' = 10 hours; '8' = 11
hours; '9' = 12 hours; 'A' = 13 hours; 'B' = 14 hours; 'C' = 15 hours; 'D' = 16 hours; 'E' = 17 hours;
'F' = 18 hours.
UL requires a 1-3 hour delay.
Backup Reporting (61)
Leaving address 61 at '0' means that reports will be transmitted to the secondary Central Station
phone number only if attempts to communicate to the primary Central Station phone number are
unsuccessful. Programming a '1' causes all reports to be transmitted to both the primary and sec-
ondary Central Station phone numbers. Programming a '2' causes reports to go to the first available
receiver.
Do not alter this entry while the digital communicator is active!
Reserved for Future Use (62)
DACT Trouble Reminder (63)
The factory default entry of '0' in address location 63 disables the trouble reminder feature. Select-
ing '1' for location 63 will cause a reminding beep (after the Silence switch is pressed) every 15 sec-
onds for active alarms and every two minutes during a DACT trouble condition. The beeps from
the onboard piezo sounder will occur until the alarm or DACT fault is cleared. The piezo sounder
will begin beeping at a rate of one second On and one second Off after 24 hours unless the DACT
fault has been cleared.
Operational Mode Selection (64)
The factory default setting is ‘0’ for latching inputs and the onboard communicator disabled. This
prevents the unit from transmitting status information to the Central Station(s).