Fire-Lite 411UDAC Fire Alarm Communicator User Manual
Page 42
![background image](/manuals/367157/42/background.png)
42
411UDAC Manual — P/N 51073:E 9/20/2013
Modes of Operation
Program Mode
Upon accessing the first event code address which is 229 (Table 3.5, “4+2 Standard and 4+2
Express Formats - Secondary,” on page 43), the following may be displayed on the Programmer’s
7-Segment Display, if the corresponding Format was selected in address 50.
The first three locations on the left of the Programmer’s display represent the memory address 229.
The last location 1 (farthest right) represents the contents of memory address 229 which is the first
digit of the event code.
The following Tables list the data which is automatically programmed for each Format that can be
selected in address 50. The addresses shown in each Table contain the event code Setting data
which is automatically programmed by the 411UDAC. To change the value, key in the new digits
and then press the [ENTER/STORE] key to save the new value. Use the Up and Down Arrow
keys to increment to the next address or decrement to the previous address.
Ademco Contact ID Format Secondary Central Station Event Codes
If ‘E’ is entered for address 50, the following data is automatically programmed for the Secondary
Central Station phone number event codes. Enter '000' for the Setting to disable the report to the
Central Station.
2291
(address) (data)
Address
Description
Setting
Channel/Input #
233 - 235
Secondary # Input Channel 1 Active Event Code
111
001
236 - 238
Secondary # Input Channel 2 Active Event Code
115
002
239 - 241
Secondary # Input Channel 3 Active Event Code
111
003
242 - 244
Secondary # Input Channel 4 Active Event Code
115
004
245 - 247
Secondary # Input Channel 1 Fault Event Code
380
001
248 - 250
Secondary # Input Channel 2 Fault Event Code
380
002
251 - 253
Secondary # Input Channel 3 Fault Event Code
380
003
254 - 256
Secondary # Input Channel 4 Fault Event Code
380
004
257 - 259
Secondary # AC Voltage Fault Event Code
301
000
260 - 262
Secondary # Earth Fault Event Code
310
000
263 - 265
Secondary # Low Battery Fault Event Code
302
000
266 - 268
Secondary # No Battery Fault Event Code
311
000
269 - 271
Secondary # Phone Line 1 Voltage Fault Event Code
351
000
272 - 274
Secondary # Phone Line 2 Voltage Fault Event Code
352
000
275 - 277
Secondary # NAC Fault Event Code
321
000
278 - 280
Secondary # Charger Fault Event Code
300
000
281 - 283
Secondary # Phone Number 1 Communication Fault Event Code
354
001
284 - 286
Secondary # Phone Number 2 Communication Fault Event Code
354
002
287 - 289
Secondary # System Off Normal Fault Event Code
308
000
290 - 292
Secondary # System Test Message
602
000
293 - 295
Secondary # System Abnormal Test Message
608
000
296 - 298
Secondary # Upload/Download Request Code
411
000
299 - 301
Secondary # Upload Successful Code
416
000
302 - 304
Secondary # Download Successful Code
412
000
305 - 307
Secondary # Upload/Download Failed Code
413
000
Table 3.4 Ademco Contact ID Format - Secondary