411UDAC Manual — P/N 51073:E 9/20/2013
Central Station Communications
Note that for Expanded Reporting, the digital communicator automatically adds the digit corre-
sponding to the Channel/Input number, and the second digit corresponding to any system trouble
condition. Only the first digit shown in Table 3.3 and Table 3.6 is programmable.
Where:
SSS or SSSS
= Subscriber ID
FA
= Fire Alarm (1st digit)
FA2
= Fire Alarm (2nd digit)
Z
= Channel/Input Number
RFA
= Fire Alarm Restore (1st digit)
RFA2
= Fire Alarm Restore (2nd digit)
TZ
= Zone Trouble (1st digit)
TZ2
= Zone Trouble (2nd digit)
RTZ
= Zone Trouble Restore (1st digit)
RTZ2
= Zone Trouble Restore (2nd digit)
TS
= System Trouble (1st digit)
TS2
= System Trouble (2nd digit)
RTS
= System Trouble Restore (1st digit)
RTS2
= System Trouble Restore (2nd digit)
P
= AC Loss (1st digit)
P2
= AC Loss (2nd digit)
RP
= AC Loss Restore (1st digit)
RP2
= AC Loss Restore (2nd digit)
V
= Fire Supervisory Condition (1st digit)
V2
= Fire Supervisory Condition (2nd digit)
RV
= Fire Supervisory Condition Restore (1st digit)
RV2
= Fire Supervisory Condition Restore (2nd digit)
X
= Test Report (1st digit)
X2
= Test Report (2nd digit)
Y
= Trouble corresponding to the following:
1
= Not Used
2
= Not Used
3
= Not Used
4
= Telco Primary Line Fault
5
= Telco Secondary Line Fault
6
= Not Used
7
= Not Used
8
= Not Used
9
= Not Used
A
= Communication Failure Primary Number
B
= Communication Failure Secondary Number
C
= Not Used
D
= Not Used
E
= Not Used
F
= Not Used
UD
= Upload/Download (1st digit)
UD2
= Upload/Download (2nd digit)
Table 4.2 Format Selection Address Explanation