beautypg.com

Fire-Lite 411UDAC Fire Alarm Communicator User Manual

Page 58

background image

58

411UDAC Manual — P/N 51073:E 9/20/2013

Central Station Communications

Ademco Contact ID Format Event Code Description

Ademco Contact ID Reporting Structure

A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble
reports in the Ademco Contact ID Reporting Structure follows:

Time

Date

Rcvr/Line ID

SSSS

QXYZ

GG CCCC

11:28

03/25

11

7777

E110

00 C001 - general fire alarm on Channel/Input 1

11:28

03/25

11

7777

E111

00 C002 - smoke detector alarm on Channel/Input 2

11:28

03/25

11

7777

E380

00 C003 - fault on Channel/Input 3

11:28

03/25

11

7777

R110

00 C001 - Channel/Input 1 alarm restored

11:28

03/25

11

7777

R111

00 C002 - smoke detector Channel/Input 2 restored

11:28

03/25

11

7777

R380

00 C003 - Channel/Input 3 fault restored

11:28

03/25

11

7777

E158

00 C004 - high temperature, Channel/Input 4

11:28

03/25

11

7777

E151

00 C004 - gas detected, Channel/Input 4