Event codes - setting entries – Fire-Lite 411UDAC Fire Alarm Communicator User Manual
Page 37

411UDAC Manual — P/N 51073:E 9/20/2013
37
Program Mode
Modes of Operation
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use
Consult the Central Station for proper Format selection. For any Format chosen, all event codes
are automatically programmed by the 411UDAC. Refer to Table 3.1, “Ademco Contact ID Format
- Primary,” on page 37, Table 3.2, “4+2 Standard and 4+2 Express Formats - Primary,” on
page 38 and Table 3.3, “All 3+1, 4+1 and 4+2 Expanded Formats - Primary,” on page 39.
Event Codes - Setting Entries
The Format selected in address 20 will cause the 411UDAC to automatically program addresses
145 - 228 with the factory default settings. Any of the Event Code settings may be altered. Consult
your Central Station prior to altering the event code settings. An entry of all zeros for any event
code will cause the communicator to NOT transmit the report. Transmission of reports to either or
both Central Station phone numbers may be disabled.
Upon accessing the first event code address (address 145) shown in Table 3.2, the following may be
displayed on the Programmer 7-Segment Display, if the corresponding Format was selected in
address 20.
The first three locations on the left of the Programmer display represent the memory address 145 of
the Format previously selected in address 20. The last location 1 (farthest right) represents the con-
tents of memory address 145 (which is the first digit of the event code).
The following Tables list the data which is automatically programmed for each Format that can be
selected in address 20. The addresses shown in each Table contain the Setting data which is auto-
matically programmed by the 411UDAC. To change the value, key in the new digit and then press
the [ENTER/STORE] key to save the new value. Use the Up and Down Arrow keys to increment
to the next address or decrement to the previous address.
Ademco Contact ID Format Primary Central Station Event Codes
If 'E' is entered for address 20, the following data is automatically programmed for the Primary
Central Station phone number event codes. Enter '000' for the Setting to disable the report to the
Central Station. The Channel # is not programmable.
1451
(address) (data)
Address
Description
Setting
Channel/Input #
145 - 147
Primary # Input Channel 1 Active Event Code
111
001
148 - 150
Primary # Input Channel 2 Active Event Code
115
002
151 - 153
Primary # Input Channel 3 Active Event Code
111
003
154 - 156
Primary # Input Channel 4 Active Event Code
115
004
157 - 159
Primary # Input Channel 1 Fault Event Code
380
001
160 - 162
Primary # Input Channel 2 Fault Event Code
380
002
163 - 165
Primary # Input Channel 3 Fault Event Code
380
003
166 - 168
Primary # Input Channel 4 Fault Event Code
380
004
169 - 171
Primary # AC Voltage Fault Event Code
301
000
172 - 174
Primary # Earth Fault Event Code
310
000
Table 3.1 Ademco Contact ID Format - Primary