Secondary central station phone number (30 - 49) – Fire-Lite 411UDAC Fire Alarm Communicator User Manual
Page 40

40
411UDAC Manual — P/N 51073:E 9/20/2013
Modes of Operation
Program Mode
Primary Central Station Number Account Code (21 - 24)
The four locations at addresses 21 - 24 default to all '0's. Valid entries are 0 - 9 and A - F. The num-
ber of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 20,
enter three digits (one digit each in locations 21, 22 and 23 - location 24 is ignored). If program-
ming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into address 20, enter four digits (one each in locations 21, 22,
23 and 24).
Primary Central Station Number 24 Hour Test Time (25 - 28)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1
takes up four locations, from addresses 25 - 28. The default is 00:00 (12:00 midnight). The limits
for each location are as follows (do not use values of A - F as entries).
25: enter 0, 1 or 2
26: enter 0 - 9
27: enter 0 - 5
28: enter 0 - 9
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (29)
The test report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the
message is to be sent every 24 hours, leave the factory default entry of '0'. If other test report times
are needed, enter 1 = 12 hour, 2 = 8 hour or 3 = 6 hour.
Secondary Central Station Phone Number (30 - 49)
Addresses 30 - 49 are factory set to 'F' (30_F to 49_F). Programming is typically done as follows:
If your phone number is 484-7161, press 4.
The display will read 30_4.
Press [ENTER/STORE] to save the entry to memory and increment to the next address
31_F.
171
Primary # Input Channel 4 Fault Restore Code
D
172
Primary # AC Voltage Fault Restore Code
9
173
Primary # Earth Fault Restore Code
A
174
Primary # Low Battery Fault Restore Code
A
175
Primary # No Battery Fault Restore Code
A
176
Primary # Phone Line 1 Voltage Fault Restore Code
A
177
Primary # Phone Line 2 Voltage Fault Restore Code
A
178
Primary # NAC Fault Restore Code
A
179
Primary # Charger Fault Restore Code
180
Primary # Phone Number 1 Communication Fault Restore Code
A
181
Primary # Phone Number 2 Communication Fault Restore Code
A
182
Primary # System Off Normal Restore Code
A
183
Primary # System Test Message
9
184
Primary # System Abnormal Test Message
F
*
185
Primary # Upload/Download Request Code
7
186
Primary # Upload Successful Code
7
187
Primary # Download Successful Code
7
188
Primary # Upload/Download Failed Code
7
* For Formats ‘B’ and ‘D’, this address is defaulted to ‘9’ instead of ‘F.’
Address
Description
Setting