beautypg.com

Rl5000 – Triton RL5000XP PC-BASED ATMS Installation Manual User Manual

Page 24

background image

24

RL5000

XP

I

NsTaLLaTION

G

UIDE

Mark the location of the cabinet

mounting holes on the concrete floor.

This is accomplished as described

below:

MARK/DRILL MOUNTING

HOLES

1. Move the ATM to the location

where it will be installed.

Open the cabinet door at least

90° degrees to improve access.

Locate the four anchor-bolt holes

(cutouts) in the bottom of the

cabinet. Use a felt-tip pen or

other marker to carefully mark

the center of each of these four

holes on the floor; these marks

will serve as guides for the anchor

bolt holes that will be drilled in

the next step. Move the ATM

aside to provide clear access to

the mounting hole marks. Center

punch each mark to help align the

drill bit.

CONCRETE STRENGTH

The floor at the installation location

should consist of commercial-grade

concrete measuring at least 2000

psi in compression strength. The

full effectiveness of the mounting

anchors depends upon meeting

this specification! Check with the

contractor/builder or owner of the

installation to verify that this re-

quirement can be satisfied.

2. Use a 1/4” diameter carbide-

tipped masonry bit to drill four

pilot holes at the drilling points

marked in the previous step. Drill

the pilot holes approximately 1/2”

deep into the floor. These holes

will help guide the 1/2” masonry

bit that will be used to drill the

anchor-bolt holes in the next step.

3. Use a 1/2” diameter carbide-tipped

masonry bit to drill four holes at

least 2 3/4” deep into the floor. Be

sure to take into account the depth

of any floor covering, such as tile

or vinyl when gauging the depth

of the anchor holes. Make sure the

holes are drilled at least

2 3/4” into the concrete floor.

4. Use a portable vacuum cleaner to

remove any dust or debris that may

have fallen into the holes during

the drilling process.

Drill anchor holes