Changing the temperature warning level, Temperature shutdown levels – Brocade ICX 6450 Stackable Switches Hardware Installation Guide User Manual

Page 81

background image

NOTE
For the ICX 6430-24P device, the low and high temperature thresholds (TA and TB) are used only for
software settings because the ICX 6430-24P model is a fanless device. There are no fan speed control
settings on the ICX 6430-24P device.

Temperature thresholds

TABLE 16

Model

Low limit temperature

TA (°C)

High limit temperature

TB (°C)

Critical (shutdown) temperature

TC (°C)

ICX 6430-24

N/A

N/A

88

ICX 6430-24P

60

65

82

ICX 6430-48

56

61

81

ICX 6430-48P

58

63

79

ICX 6450-24

66

71

83

ICX 6450-24P

59

64

88

ICX 6450-48

64

69

76

ICX 6450_48P

56

61

79

Changing the temperature warning level

To change the temperature at which the device sends a syslog message and an SNMP trap, enter a
command similar to the following at the Privileged EXEC level of the CLI.

Brocade# temperature warning 1 82

Syntax: temperature warning stack-id value

The stack-id can be a value from 1 through 8.

The value variable is the temperature warning level, in Celsius. You cannot set this level higher than
83°C . The temperature warning level must be at least five degrees Celsius less than the temperature
shut down level, which is automatically set by the device.

The following console and syslog message is displayed when the temperature reaches the warning
level:

!!! Temperature is over warning level on stack unit 1!!!

Temperature shutdown levels

When the temperature crosses the critical (shutdown) threshold levels, the device will reset after 5
minutes. The following console and syslog message is displayed:

!!! Temperature is over shutdown level, please shutdown your stack unit 1 to avoid hw

damage!!!