Appendix 1 Specifications of PR300

*: The setting of the voltage range can be changed.

**: The primary voltage of VT.

Power Items and Equations

Phase and wire system

Single-phase two-wire
system

Single-phase three-wire
system

Three-phase three-wire
system

Three-phase four-wire
system

Three-phase four-wire
system (2.5 element)

Apparent Power

VA = V

×A

VAi = Vi

×Ai

i = 1, 2

ΣVA = VA1+VA2

VAi = Vi

×Ai

i = 1, 3

ΣVA = 3/2(VA1+VA3)

VAi = Vi

×Ai

i = 1, 2, 3

ΣVA = VA1+VA2+VA3

VAi = Vi

×Ai

i = 1, 3

ΣVA = 3/2(VA1+VA3)

Reactive Power

(without using reactive power meter method)

Q = ((VA)

2

−P

2

)

Qi = ((VAi)

2

−Pi

2

)

i= 1, 2

ΣQ=Q1+Q2

Qi = ((VAi)

2

−Pi

2

)

i=1, 3

ΣQ=Q1+Q3

Qi = ((VAi)

2

−Pi

2

)

i=1, 2, 3

ΣQ=Q1+Q2+Q3

Qi= (

3/2 (VAi)

2

−Pi

2

)

i=1, 3

ΣQ=Q1+Q3

Power Factor

ΣP / ΣVA

(without using reactive
power meter method)

(V and A are rms values.)

* For distorted wave input, there may be differences between the PR300 and a measuring instrument that uses a different measurement principle.

Input Specifications

Phase and wire system

Universal three-phase three-wire system (switch the setting from single-phase two-wire system,
single-phase three-wire system, or three-phase three-wire system)

Universal three-phase four-wire system (switch the setting from single-phase two-wire system,
single-phase three-wire system, three-phase three-wire system, or three-phase four-wire system)

Three-phase four-wire system (2.5 element)

Frequency

45 to 65Hz

Rated input voltage

120 V; voltage range: 150 V

(*)

: 900kV

(**)

240 V; voltage range: 300 V

(*)

: 1800kV

(**)

480 V; voltage range: 600 V

(*)

: 3600kV

(**)

Allowable input voltage Within the voltage range

Rated input current

1 A; current range: 1 A (fixed): 32kA

(***)

5 A; current range: 5 A (fixed): 160kA

(***)

Allowable input current 1.2 times the current range (continuous); twice the current range (10 seconds); 10 times the

current range (3 seconds)

Rated input power and measuring range (when VT and CT are used, their respective secondary values)

Input

(AC)

120V/1A

120V/5A

240V/1A

240V/5A

480V/1A

480V/5A

Rated power

100W

500W

200W

1000W

400W

2000W

Input

measuring

range

–120 to 120W

–600 to 600W

–240 to 240W

–1200 to 1200W

–480 to 480W

–2400 to 2400W

Approximate consumed VA

Voltage

0.2VA

0.4VA

0.8VA

Current

0.2VA

Input

(AC)

120V/1A

120V/5A

240V/1A

240V/5A

480V/1A

480V/5A

Rated power

200W

1000W

400W

2000W

800W

4000W

Input

measuring

range

–240 to 240W

–1200 to 1200W

–480 to 480W

–2400 to 2400W

–960 to 960W

–4800 to 4800W

Approximate consumed VA

Voltage

0.2VA/

phase

0.4VA/

phase

0.8VA/

phase

Current

0.2VA/

phase

Input

(AC)

120V/1A

120V/5A

240V/1A

240V/5A

480V/1A

480V/5A

Rated power

300W

1500W

600W

3000W

1200W

6000W

Input

measuring

range

–360 to 360W

–1800 to 1800W

–720 to 720W

–3600 to 3600W

–1440 to 1440W

–7200 to 7200W

Approximate consumed VA

Voltage

0.2VA/

phase

0.4VA/

phase

0.8VA/

phase

Current

0.2VA/

phase

Input

(AC)

240V/1A

240V/5A

Rated power

200W

1000W

Input

measuring

range

–240 to 240W

–1200 to 1200W

Approximate consumed VA

Voltage

0.2VA/

phase

Current

0.2VA/

phase

Single-phase two-wire system

Single-phase three-wire system

Three-phase three-wire system

Three-phase four-wire system

*

*

*

*

Input specification of 1A AC is not available for 2.5 element.

When VT and CT are used, the input measuring range of the primary input power is smaller
than 10 GW, and the value calculated by the following equation is within the input measuring
range above.
Input measuring range (W) =

Primary input power (W)

VT ratio ϫ CT ratio

***: The primary current of CT.