Setting Demand Measurement Conditions

Demand Alarm Point screen

11

12

14

15

13

Demand Alarm Release
Function screen

Demand Alarm Release
Function Setting screen

Demand Alarm Release
Function Setting screen

The screen changes to the one
for setting the parameter .

Demand Alarm Release
Function screen

Demand Alarm Release
Function Setting screen

The parameter
(demand alarm release function)
appears.

The setpoint is confirmed and the
PR300 returns to the Demand Alarm
Point screen.

The setpoint is confirmed and the PR300 returns
to the Demand Alarm Release Function screen.

Demand alarm point setting
completed.

Demand alarm release function
setting completed.

Press once.

Press once.

Using or ,
select the setpoint.

Press once to
blink the setpoint.

Press once while
the setpoint is blinking.

To return to the Demand Measurement

Menu screen, press

.

To return to the Measured Value

screen, hold down

.

If you do not operate any key for more
than 5 minutes on the Parameter
screen, the PR300 automatically
returns to the Measured Value screen.

NOTE

If the demand period and demand alarm mask time do not satisfy the following conditional expres-
sion, the updated demand period or demand alarm mask time will not be incorporated but revert to
the value before change.

Demand alarm mask time

Ϲ

Demand period

Parameter Setting Types and Ranges

Demand measurement menu

Demand power/current

Demand period

Demand alarm mask time

Demand alarm point

Demand alarm release
function

Selection

Integral

numeric

value

Integral

numeric

value

Integral

numeric

value

Selection

Active power

Current

1 to 60 (min)
(Demand alarm mask time to 60) (min)

1 to 59 (min)
(1 to demand period) (min)

1 to 1000 (kW): When active power is
selected, or 1 to 1000 (A): When current is
selected

Automatic release

Manual release

Active power

1

100

Automatic

release

30

Menu to shift to the parameters of
demand measurement

Parameter Symbol

Parameter Name

Setting

Type

Setting Range (Details)

Initial Value

(Factory-set

Value)