Other wiring, Analog output, Demand alarm output – Yokogawa PR300 Power and Energy Meter User Manual
Page 15: Demand alarm release, Ethernet communication, Integration control signal, Palse output, Rs-485 communication, Other wiring -8

1-8
IM 77C01E01-01E
1.3
Wiring
Other Wiring
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
a
b
c
d
e
f
Color
Description
Color
Description
Link LED
Off
Stopped
Active LED
Off
Stopped
Orange
10Mbps
Orange
Half
duplex
Green
100Mbps
Green
Full
duplex
Ethernet communication
10BASE-T
100BASE-TX
RJ45 connector
Pulse output
Contact capacity
30V DC, 200mA
(resistive load)
14
13
RS-485 communication
*1
A
؊
R:120
⍀(built-in)
TERM
B
؉
SG
17
18
19
20
R
Analog output
Output signal:
4 to 20 mA DC
12
11
+
−
+
−
Contact capacity
30V DC, 200mA
(resistive load)
Demand alarm output
ALM
+
ALM
−
16
15
Optional integration
control signal or demand
alarm release
*2
DI
؉
DI
؊
22
21
Switching between 10BASE-T and
100BASE-TX takes place automatically.
Switching between half and full duplex
takes place automatically.
When terminating, short-circuit
terminals 17 and 18 with the
shorting bar.
*1 If Ethernet communication is used, the
RS-485 communication interface is used
specifically for the Ethernet-serial gate-
way function.
*2 In the case of the PR300 with the
demand measuring function, the demand
alarm release is selected.
Voltage signal
ON signal: 4.5 to 25 V DC
OFF signal: within
Ϯ1V DC