Setting the VT and CT Ratios

Setting the CT Ratio

This section explains how to set the CT ratio by taking as an example the case when the CT ratio is
changed from the initial value (1.00) to 10.00.

Operation

Operation

2

3

4

5

CT Ratio Setting screen

The alterable digit blinks.

6

7

CT Ratio Setting screen

CT Ratio Setting screen

CT Ratio screen

Press once to
blink the setpoint.

CT Ratio Setting screen

Press once to fix the
position of the decimal point.

Using or ,
change the setpoint.

Measured Value screen

1

The parameter (VT ratio)
appears.

VT Ratio screen

Press once.

Current value

The parameter (CT ratio)
appears.

CT Ratio screen

Press once.

The screen changes to the one
for setting the parameter
and the decimal point blinks.

Hold down for at
least 3 seconds.

To move the decimal point, use the
following keys:

To the left

To the right

Press once while
the setpoint is blinking.

The setpoint is confirmed and the
PR300 returns to the CT Ratio screen.

CT ratio setting completed.

To return to the Measured Value

screen, hold down

.

If you do not operate any key for more
than 5 minutes on the Parameter
screen, the PR300 automatically
returns to the Measured Value screen.

Setpoint

To move to the digit to be changed,
use the following keys:

To the left

To the right

To re-set the parameter:

Press any key other than

while all digits of the
setpoint are blinking.
The PR300 returns to the initial
setting screen.

Parameter Setting Types and Ranges

Parameter Symbol

Parameter Name

Setting

Type

Setting Range (Details)

Initial Value

(Factory-set

Value)

CT ratio

Floating-point

numeric

value

0.05 to 32000

1.00

NOTE

Set the VT and CT ratios so that the value of “secondary rated power

ϫ

VT ratio

ϫ

CT ratio” is smaller

than 10 GW. If this value exceeds 10 GW, the updated VT or CT ratio will not be incorporated but revert
to the current value before change.