Yokogawa EJX930A User Manual
Page 89
<5. Parameter Summary>
5-7
IM 01C25R02-01E
Function
Label
Item
Contents
Default value Handling
*
1
Master test
Master test
Software reset and self test
M
Message
Message
Message
32 alphanumerics
As specified
W
Model
Model
Model
W
Number of
requested
preambles
Num req preams
Number of requested preambles
R
Num resp preams
HART 7
Number of response preambles
5
W
Optional
function
Option Password
Optional function activation
password
W
Piping
orientation
H/L Swap
Impulse piping accessing direction Normal or Reverse
Normal
R
Poll address
Poll addr
Poll address for multidrop use
0 to 15(HART 5), 0 to
63(HART 7)
0
W
Loop current mode
HART 7
Loop current mode in Multi Drop
mode
(Disabled, Enabled)
Disabled
W
Process Alerts Digital Output
Display of contact output
Off or On
Off
W
DO Frequency
Frequency of Digtal Output
W
DO Select
Contact output select
Combination of Pres, SP,
Temp, and Flow
W
DO Signal type
Signal type select
On When Al. Detect, Off
When Al. Detect, Scaled
Pulse, or Frequency
W
DO Test
Test output contact
Status High, Status Low,
Freguency, Exit
M
Test Auto Release
Time
“Flow simulation”, “DO Test”,
“Device Variable Simulation”
and “Test output” duration time
selection.
10min, 30min, 60min, 3h,
6h, 12h
10min
W
Pres Alert Mode
Alert Mode for differential pressure Off, Hi Al Detect,Lo Al Detect,
Hi/Lo Al Detect
Off
W
Pres Hi Alert Val
High alert value for differential
pressure
Set the threshold value for
high side alarm
W
Pres Lo Alert Val
Low alert value for differential
pressure
Set the threshold value for
low side alarm
W
SP Alert Mode
Alert Mode for static pressure
Off, Hi Al Detect,Lo Al Detect,
Hi/Lo Al Detect
Off
W
SP Hi Alert Val
High alert value for static pressure
Set the threshold value for
high side alarm
W
SP Lo Alert Val
Low alert value for static pressure
Set the threshold value for
low side alarm
W
ET Alert Mode
Alert Mode for external temperature Off, Hi Al Detect,Lo Al Detect,
Hi/Lo Al Detect
Off
W
ET Hi Alert Val
High alert value for external
temperature
Set the threshold value for
high side alarm
W
ET Lo Alert Val
Low alert value for external
temperature
Set the threshold value for
low side alarm
W
Flow Alert Mode
Alert Mode for flow
Off, Hi Al Detect,Lo Al Detect,
Hi/Lo Al Detect
Off
W
Flow Hi Alert Val
High alert value for flow
Set the threshold value for
high side alarm
W
Flow Lo Alert Val
Low alert value for flow
Set the threshold value for
low side alarm
W
Process
variables
Change 4V Assgn
HART 5
Change the allocation to 4V
M
4V
HART 5
4V value
Unit specified in 4V Unit
R
4V is
HART 5
Current 4V
R
Amp temp
Amplifier temperature
R
Cap temp
Capsule temperature
R
Engr Disp
User scaled value
Unit specified in Set Engr Unit
R
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)