Yokogawa EJX930A User Manual
Page 70
<4. Diagnostics>
4-20
IM 01C25R02-01E
# Parameter name Default value
Explanation
28 Ref fSPl
Value of
fSPl obtained under normal condition.
29 Ref fSPl Status
Status of
fSPl obtained under normal condition.
30 Ref fSPh
Value of
fSPh obtained under normal condition.
31 Ref fSPh Status
Status of
fSPh obtained under normal condition.
32 Ref BlkF
Value of
BlkF obtained under normal condition.
33 Ref BlkF Status
Status of
BlkF obtained under normal condition.
34 Ref DPAvg
Value of
DPAvg obtained under normal condition.
35 Ref DPAvg
Status
Status of
DPAvg obtained under normal condition.
36 Lim fDPmax
Refer to
Table 4.3
Upper limit for
Ratio fDP to detect the blockage.
Writable only when
Diag Mode is "Stop".
37 Lim fDPmin
Lower limit for
Ratio fDP to detect the blockage.
Writable only when
Diag Mode is "Stop".
38 Lim fSPlmax
Upper limit for
Ratio fSPl to detect the blockage.
Writable only when
Diag Mode is "Stop".
39 Lim fSPlmin
Lower limit for
Ratio fSPl to detect the blockage.
Writable only when
Diag Mode is "Stop".
40 Lim fSPhmax
Upper limit for
Ratio fSPh to detect the blockage.
Writable only when
Diag Mode is "Stop".
41 Lim fSPhmin
Lower limit for
Ratio fSPh to detect the blockage.
Writable only when
Diag Mode is "Stop".
42 Lim BlkFmax
Upper limit for
BlkF to detect the blockage.
Writable only when
Diag Mode is "Stop".
43 Lim BlkFmin
Lower limit for
BlkF to detect the blockage.
Writable only when
Diag Mode is "Stop".
44 Lim DPAvgmax
Upper limit for
DPAvg. Writable only when Diag Mode is "Stop".
45 Lim DPAvgmin
Lower limit for
DPAvg. Writable only when Diag Mode is "Stop".
46 Ref Lim fDPmin
7.0E-10
Lower limit to judge whether
Ref fDP is available for ILBD operation.
Writable only when Diag Mode is "Stop".
47 Ref Lim fSPmin
1.0E-10
Lower limit to judge whether
Ref fSPl and Ref fSPh are available for ILBD
operation.
Writable only when Diag Mode is "Stop".
48 Ref Lim BlkFmax 0.5
Upper limit to judge whether
Ref BlkF is available for ILBD operation.
Writable only when Diag Mode is "Stop".
49 Status group 9
Refer to Table 4.5.
50 Status group 10
Refer to Table 4.5.
51 CRatio fDP
Ratio fDP is compensated by following formula and used as treatable monitoring
value when the flow change is too large or small.
Sqrt (
fDP / Ref fDP) X | Ref DPAvg / DPAvg |
When compensation is selected in
Diag DP Comp, CRatio fDP is used as
monitoring value.
52 CRatio fDP
Status
Status of
CRatio fDP
53 NRatio fDP
When Non-compensation is selected in
Diag DP Comp, NRatio fDP is used as
monitoring value.
NRatio fDP = Sqrt (fDP / Ref fDP)
54 NRatio fDP
Status
Status of
NRatio fDP
55 Diag DPComp
0:
Compensation
Whether
fDP is referred by CRatio fDP or NRatio fDP is selected.
56 Diag Applicable
After the reference value is obtained, the applicable blockage detection is
displayed on this parameter.