5 alarm and alert setting, 5 alarm and alert setting -12 – Yokogawa EJX930A User Manual

Page 62

background image

<4. Diagnostics>

4-12

IM 01C25R02-01E

Bit

DD

(HART 5/HART 7)

DTM (HART 7)

DTM (HART 5)

Category

0 Not used

Not used

1 Not used

Not used

2 A Blocking

A Blocking

ILBD

3 Large Fluct L

Large Fluctuation

of Low Side

4 Large Fluct H

Large Fluctuation

of High Side

5 L Side Blocking

Low Side Blocking

6 H Side Blocking

High Side

Blocking

7 B Blocking

B Blocking

8 Invalid Ref F

Invalid Ref BlkF

9 Invalid Ref SPH

Invalid Ref fSPh

10 Invalid Ref SPL

Invalid Ref fSPl

11 Invalid Ref DP

Invalid Ref fDP

12 ILBD over range Outside Diagnosis

Range

13 FT low alarm

Flg Temp Low

Alarm

Heat trace

monitoring

14 FT high alarm

Flg Temp High

Alarm

15 Not used

Not used

Note: FT indicates the flange temperature.

ILBD over range (Outside Diagnosis

Range)

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Diag/Service → Diag

Parameters → ILBD Parameters →

Configuration → Diag Lim →

DTM (HART 5) Diag and Service → Advanced Diag

Configurations → Impulse Line

Blockage Detection → Threshold →

1) Lim DPAvgmax

Lim DPAvgmax is the upper limit of the

diagnostic capability range. The limit value can

be changed when

Diag Mode is “Stop”.

DPAvg indicates the ratio of the average of

differential pressure to the EJX maximum span

regarded as 1. When

DPAvg exceeds this

limit, “ILBD over range” is generated so that the

blockage detection becomes impossible.

2) Lim DPAvgmin

Lim DPAvgmin is the lower limit of the

diagnostic capability range. The limit value can

be changed when

Diag Mode is “Stop”.

When

DPAvg is below this limit, “ILBD over

range” is generated so that the blockage

detection becomes impossible.

4.2.2.5 Alarm and Alert Setting

The abnormal results as the blockage detection and

high/low flange temperature (heat trace monitoring)

are given through an analog alert or the LCD

display of alarm status. Before performing the ILBD

operation, it is necessary to set the alarm and alert

according to the following procedure.

Storage of Abnormal results

(Diag Error)

Alarm Masking

(Diag Option)

Outside Diagnosis Range/

Invalid Ref xx

Masking

Alarm on

Analog Output

Alarm on

Status Output

Device Status

Field Device More Status Available

Additional Device Status

(Status group 9 and 10)

Alarm Display

on LCD

F0408.ai

Figure 4.6

Alarm and Alert Setting

Alarm Status

When the algorithm of ILBD and Heat trace

monitoring detect the abnormality, the result is

stored in

Diag Error. The alarm status based on the

detected abnormality is displayed to

Diag Error.

(Displayed to

Impulse Line Blockage Detection

and

Heat Trace for DTM(HART 5))

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Diag/Service → Diag

Parameters → Diag Error →

DTM (HART 5) Diag and Service → Advanced Diag

Alerts → Diag Error