beautypg.com

13 test output, simulation, and squawk, Test output, simulation, and squawk -26 – Yokogawa EJX930A User Manual

Page 37

background image

<3. Parameter Setting>

3-26

IM 01C25R02-01E

Example of Pulse Output

F0307.ai

T = 1sec

The number of pulses (PPS)

(*1) Example of scaled pulse

Pulse Rate =10kg

(*2) Example of freqency output

Configuration: Freq at 100% =10000Hz

Flow Rate: URL =100% 10000(PPS)

Scaled pulse

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Signal condition → Total Flow →

DTM (HART 5)

Configuration → Total Flow →

→ Total Flow Unit Select the unit of total flow
→ Pulse rate

Set the volumetric flow rate or

mass flow rate per one pulse.

Scaled pulse 10 kg Set

1) Enter “kg” to

Total Flow Unit

2) Enter “10” to

Pulse rate

Frequency output

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Signal condition → Total Flow →

DTM (HART 5)

Configuration → Total Flow →

→ Freq at 100%

Set the number of output pulse per

second at 100% flow rate.

Max. frequency: 10kHz

Duty cycle: Approx 50%

Freq at 100% is 10000 Hz Set

1) Enter “10000” to

Freq at 100%

3.3.13 Test Output, Simulation, and Squawk

NOTE

Fixed current output, DO Test, Flow Simulation

Mode, and Device Variable Simulation Function

continue for a given holding time, then is

released automatically. Even if the HART

configuration tool power supply is turned off or

the communication cable is disconnected, the

test output will continue for that time.

The holding time can be selected from 10 min*,

30 min, 60 min, 3 hour, 6 hour or 12 hour.

*: Default value.
• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Diag/Service

→ Test Auto Release Time

DTM (HART 5)

Diag and Service → Service

→ Test Auto Release Time

(1) Fixed current output
This feature can be used to output a fixed current

for loop checks. The available range for test output

depend on the settings for the

AO lower limit and

AO upper limit parameters, whose limit is from

3.8mA (-1.25%) to 21.6mA (110%).

Refer to the subsection 3.3.1 about the setting of

AO lower limit and AO upper limit.

While this function works, “TEST” is displayed on

the integral indicator.

In the case of using DD (HART 5/HART 7)

and DTM (HART 7)

Call up the test output parameter (Loop test) and

select the output signal.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Diag/Service →

Test → Loop test →

Display Item

Contents

4mA

Output a 4mA DC signal

20mA

Output a 20mA DC signal

Other

Set a desired output signal value

End

Exit

In the case of using DTM (HART 5)

Call up the test output parameter (Loop test) and

select either manual test or auto test, and set the

current value.

This manual is related to the following products: