Yokogawa EJX930A User Manual
Page 88

<5. Parameter Summary>
5-6
IM 01C25R02-01E
Function
Label
Item
Contents
Default value Handling
*
1
Event
Notification
Latched Device
Status
HART 7
Device status when event occurred
W
Latched Status
group 1 to 11
HART 7
Field device status when event
occured
W
Latched Ext dev
status
HART 7
Latched Device
Diagnostic Status 0
HART 7
Latched Device
Diagnostic Status 1
HART 7
Latched AO
saturated
HART 7
Latched AO fixed
HART 7
Flow setup
Flow Damp
Damping time constant for flow
0.00 to 100.00 sec
W
Flow LRV
Lower range value for flow
W
Flow URV
Upper range value for flow
W
Vol Flow Base Dens Volume Flow Base Density Value
W
Flg temp
Flg temp
Calculated flange temperature
value
RG
Flg temp Coef Flg temp Coef
0
WG
Flg temp Lim Flg temp Hi Alarm
Val
Upper limit of Flange temperature
120 °C (deg C)
WG
Flg temp Lo Alarm
Val
Lower limit of Flange temperature
-40 °C (deg C)
WG
Fluct Variables fDP
Average value of the sum of
squares of differential pressure/
pressure fluctuations
RG
fDP Status
Status of fDP
RG
fSPl
Average value of the sum of
squares of low-pressure-sidestatic
pressure fluctuations
RG
fSPl Status
Status of fSPl
RG
fSPh
Average value of the sum of
squares of high-pressure-side
static pressure fluctuations
RG
fSPh Status
Status of fSPh
RG
Flg temp
Flg temp
Calculated flange temperature
value
RG
Keypad Input
Change PV Assgn
Change the allocation to PV
M
PV Damp
Damping time constant for PV
W
PV is
Current PV
R
PV LRV
Lower range value for PV
W
PV URV
Upper range value for PV
W
Loop test
Loop test
Test output setting
Within AO lower and upper
limits
M
Test Auto Release
Time
“Flow simulation”, “DO Test”
and “Test output” duration time
selection.
10min, 30min, 60min, 3h,
6h, 12h
10min
W
Low cut
Low cut
Low cut
0.00 to 20.00%
10.00%
W
Low cut mode
Low cut mode
Off or On
Off
W
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)