<3. Parameter Setting>

3-18

IM 01C25R02-01E

F0304.ai

Available displays Description and related parameters

% of PV range

(PV %)

Indicates input value depending on

the set PV range (

PV LRV and PV

URV).

PV % 92.4 %

Flow rate

(Flow)

Indicates values of calculated flow

with the indication limits –99999 to

99999.

Flow 26.0 kg/h

Input differential

pressure

(Pres)

Indicates values of input differential

pressure with the indication limits

–99999 to 99999.

PRES 45.6 kPa

Input static pressure

(SP)

Indicates values of input static

pressure with the indication limits

–99999 to 99999.

SP

6.178 MPa

Input ext. temperature

(ET)

*1

Indicates values of input external

temperature with the indication limits

–99999 to 99999.

ET

22.95 degC

User set scaled PV

(Engr Disp)

*2

Indicates values depending on the

engineering range (

Engr LRV and

Engr URV) with the unit (Engr Unit).

Engr LRV 0.0

Engr URV 45.0

Engr exp x100

Engr Unit m3/min

Engr point 1

Total flow

(Total Flow)

*3

Indicates values of calculated total

flow with the indication limits as

follows.

0 to 9.99E29 (Normal mode)

0 to 999999 (Cyclic mode)

Total Flow 123.45 kg

F

F

P

SP

T

F

*1 : “EXT. TEMP” for DD and DTM (HART 5)

*2 : “ENGR. PV” for DD and DTM (HART 5)

*3 : “TOTAL FLOW” for DD and DTM (HART 5)

See (a) through (d) for the setting procedures.

a. Display Selection

At

Disp select, select the variable that the

parameter Disp 1 will display on the integral

indicator.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Display condition → Disp select →

Disp 1

DTM (HART 5) Configuration → Local Display →

Disp Out 1

→ Disp 1 /

Disp Out 1

Select desired display from seven

kinds of displays shown above.

Set Disp 2, Disp 3 and Disp 4 in the same way if

necessary.

In addition to the above item, "Not used" is also

displayed as a selection item.
b. Cyclic Display
Up to four displays can be displayed cyclically in the

order of the parameter number.
c. Display Resolution
User can change the position of decimal point

which is shown on the integral indicator.

• Procedure to call up the

Disp % reso display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Display condition →

DTM (HART 5) Configuration → Local Display →
→ Disp %

Reso

Select the decimal point position of

PV%

Normal: Display one digit below the

decimal point

High Resolution: Display two digits

below the decimal point

• Procedure to call up the

Flow Disp point , Pres

disp point , SP disp point , ET disp point , TF

disp point display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Display condition → Disp Condition

DTM (HART 5) Configuration → Local Display →
→ Flow Disp

point

Select the decimal point position of

flow rate (0, 1, 2, 3 or 4)

→ Pres disp

point

Select the decimal point position of

differential pressure (0, 1, 2, 3 or 4)

→ SP disp

point

Select the decimal point position of

static pressure (0, 1, 2, 3 or 4)

→ET disp point Select the decimal point position of

external temperature (0, 1, 2, 3 or 4)

→TF disp point Select the decimal point position of

total flow (0, 1, 2, 3 or 4)

d. User Setting of Engineering Unit and Scale
[For DD (HART 5/7) and DTM (HART 7)]

Engr disp range parameters allow the engineering

unit and scale to be displayed. At

Set Engr Unit,

the following engineering units can be selected from

a list.