<5. Parameter Summary>
5-4
IM 01C25R02-01E
Function
Label
Item
Contents
Default value Handling
*
1
Display setup Bar Indicator
Bar indicator
Off or On
On
W
Disp Out 1/Disp1
LCD output 1
PV %, Flow, Pres, SP, EXT.
TEMP, ENGR.PV, or TOTAL
FLOW
PV %
W
Disp Out 2/Disp2
LCD output 2
PV %, Flow, Pres, SP, EXT.
TEMP, ENGR.PV, TOTAL
FLOW, or Not used
Not used
W
Disp Out 3/Disp3
LCD output 3
(Ditto)
Not used
W
Disp Out 4/Disp4
LCD output 4
(Ditto)
Not used
W
Disp % Reso
% display resolution
Normal or High resolution
Normal
W
Engr exp
User set exponent
---, x10, x100, x1000
--- or as
specified
W
Engr LRV
User set lower range value
Unit specified in Set Engr Unit As specified
W
Engr point
Decimal place for user set
0 to 4
2
W
Engr URV
User set upper range value
Unit specified in Set Engr Unit As specified
W
ET disp point
Decimal place for external
temperature
0 to 4
2
W
Flow disp point
Decimal place for flow
0 to 4
2
W
Modify Engr Unit
User set engineering unit
M
Pres disp point
Decimal place for differential
pressure
0 to 4
2
W
Set Engr Unit
Engineering unit select
M
SP disp point
Decimal place for static pressure
0 to 4
2
W
TF disp point
Decimal place for total flow
0 to 4
2
W
Squawk
HART 7
Squawk
Specify the device under the
communication (turn the LCD
on).
M
DP setup
Pres Damp
Damping time constant for DP
0.00 to 100.00 sec
W
Pres Min Span
Minimum span for differential
pressure
R
Pres LRV
Lower range value for differential
pressure
W
Pres LSL
Lower sensor limit for differential
pressure
R
Pres URV
Upper range value for differential
pressure
W
Pres USL
Upper sensor limit for differential
pressure
0 to 4
R
Error log
Error log Clear
Clear error records
M
Error log view
Error records
Log1 (latest) to log4
M
ET setup
ET Damp
Damping time constant for ET
0.00 to 100.00 sec
W
ET Fixed
External temperature fix mode
No,Yes, or FALL BACK
No
W
ET Min Span
Minimum span for external
temperature
R
ET LRV
Lower range value for ET
W
ET LSL
Lower sensor limit for ET
R
ET URV
Upper range value for ET
W
ET USL
Upper sensor limit for ET
R
Fixed ET Val
Temperature value at ET fix mode
20 °C (deg C)
W
*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)