<4. Diagnostics>

4-13

IM 01C25R02-01E

When the level range that can be measured by the

transmitter with 100 kPa span is –80 to 80 kPa, the

limits are set as follows.

Lim DPAvgmax: 0.80

Lim DPAvgmax: –0.80

1.000

0.000

0.80

-0.80

-1.000

Detectable
range

DPAvg

ILBD over range

ILBD over range

F0409.ai

Invalid Ref F, SPH, SPL, or DP

This alarm indicates that the reference value under

normal condition is invalid. If

Ref F is invalid, the

blockage detection excluding

BlkF is carried out.

If blockage detection function based on

BlkF is

required, obtain the reference value again.
Also when

Ref DPAvg is below Lim DPAvgmin

or exceeds

Lim DPAvgmax, all reference value

becomes invalid so that “Invalid Ref DP”, “Invalid

Ref SPL”, “Invalid Ref SPH”, and “Invalid Ref F” are

generated.

Alarm Masking

Diag Option

The alarms linked to an analog alert and LCD

display are selected by

Diag Option.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Diag/Service → Diag

Parameters → Diag Option →

DTM (HART 5) Diag and Service → Advanced Diag

Configurations → Impulse Line

Blockage Detection → Diag Option →

The bit of

Diag Option is corresponding to that

of

Diag Error. The following alarms are set at

the factory setting, which is corresponding to

hexadecimal 0x08FC.

DD

(HART 5/HART 7)

DTM (HART 7)

DTM (HART 5)

A Blocking

A Blocking

Large Fluct L

Large Fluctuation of Low Side

Large Fluct H

Large Fluctuation of High Side

L Side Blocking

Low Side Blocking

H Side Blocking

High Side Blocking

B Blocking

B Blocking

Invalid Ref DP

Invalid Ref fDP

To Link the alarm to an analog alert and LCD

display, follow the procedure below.
1) Set “Stop” to

Diag Mode.

2) Check each checkbox of the alarm, which is

selectable from bit 2 to 14.

Note: Set to “Calculation” after setting the parameter.

Alert Setting

Diag Out Option

When an alert regarding the impulse line blockage

or high/low flange temperature is generated, the

output value of 4-20 mA analog signal can be

changed.

Mode

Function

Off

Keeping PV measurement. The alert is not

reflected to 4-20 mA analog signal.

Burnout

The analog signal is shifted to the value of

AO upper limit or AO lower limit when an

alert is generated.

The shifted direction follows Burnout switch

setting.

Fall back

The analog signal is hold to the specific

value,

Diag Fixed Out Val, when an alert is

generated.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Diag/Service → Diag

Parameters → Diag Output → Diag

Out Option →

DTM (HART 5) Diag and Service → Advanced Diag

Configurations → Diag Output → Diag

Out Option →

Diag Fixed Out Val

This parameter is used when “Fall back” is selected

to

Diag Output Option.

When an alert is generated, the 4-20 mA analog

signal is held on the value specified by this

parameter.
The value can be entered within 3.8 to 21.6 mA.