beautypg.com

Series 922 error codes/alarms, Error codes, 87 – Watlow Series 922 User Manual

Page 87

background image

WATLOW Series 922 User's Manual

87

Appendix

ER2 Error Codes and Actions

1

922 transmit buffer overflow. Clear error,
retransmit.

2

922 receiver buffer overflow. Pro-
tocol or syntax violation, retransmit.

3

Framing/overrun error. Check baud
rate, parity, stop bits.

5

Parity error. Check baud rate, parity,
stop bits.

6

Talking out of turn. STX protocol
violation, retransmit.

7

Invalid reply error. Figure out com-
munications, retransmit.

20 Command not found. Check your

program.

21 Parameter not found. Check your

program.

22 Incomplete command line. Syntax

error, retransmit.

23 Invalid character. Syntax error,

retransmit.

24 Number of characters overflow.

Numeric syntax error, retransmit.

25 Input out of limit. Transmitted value

too large or small, retransmit.

26 Read only command. Cannot input

a value for that parameter, retransmit.

27 No Channel 2 available error.
28 Write only error. A read was attempted on

a parameter that can only be written to.

30 Request to run invalid. Verify a run

condition.

31 Request to hold invalid. Verify a

hold condition.

32 Command invalid in run mode. Cannot

enter values in run mode, retransmit.

33 Self test mode not active. Check to see

that DIP switch #6 is ON.

35 Number of steps stored is > or = to 99.

Enter steps only to 99.

36 No file found. Check your program,

retransmit.

37 No step found. Check your program.
38 No asterisk input allowed. Follow proper

format for entering asterisks.

39 Infinite loop error. Check the number of

consecutive loops, retransmit.

40 File change error. An attempt to resume a

changed file occurred. Check your
program.

Series 922 Error Codes/Alarms

ER1 Error Codes and Actions

1

Internal RAM failure. Contact factory.

2

External RAM failure. Contact factory.

3

Bad battery error. Contact factory.

4

Channel 1 A/D conversion error; check sensor or
contact factory.

5

Channel 2 A/D conversion error; check sensor or
contact factory.

6

Ground A/D conversion error; contact factory.

7

High reference A/D conversion error, contact
factory.

8

Channel 1 interpolation/overrange. Check
specification for sensor input range.

9

Channel 2 interpolation/overrange. Check
specification for sensor input range.

10 D/A gain error. Contact factory.
11 Channel 1 zero error. Contact factory.
12 Channel 1 gain error. Contact factory.
14 Channel 2 zero error. Contact factory.
15 Channel 2 gain error. Contact factory.
18 Stack overflow error. Contact factory.

NOTE:

If an error or alarm flashes on the display, press

the enter key to stop the flashing for 5 minutes. To clear
the alarm or error, go to the system menu and press
enter on the appropriate prompt.