Setup prompts and description, Table 9, Setup menu – Watlow Series 922 User Manual
Page 46: Setup
46
WATLOW Series 922 User's Manual
How To Program the Series 922, Chapter 6
SETUP Menu
Table 9 -
SETUP Prompts and
Description.
Prompt
Description
Range
Default
Your Settings
ACCESS = (1) PID
To enter PID parameters, use ACCESS (1) & press ENTER.
CH1
PB1H
Enter the Channel 1 Proportional Band value, Heating.
0-900°F/0-500°C/0-500Units 45°F/25°C/25U
RS1H
Enter the Channel 1 Reset value, Heating.
0.00 - 5.00 repeats/minute
0.00
Not displayed if PB1H = 0.
RT1H
Enter the Channel 1 Rate value, Heating.
0.00 - 5.00 minutes
0.00
Not displayed if PB1H = 0.
CT1H
Enter the Channel 1 Cycle Time value, Heating.
1 - 60 seconds
5
Not displayed if PB1H = 0. Dependent on output & OUT1.
RB1H
Enter the Channel 1 Rate Band value, Heating.
0 - 7 times PB1H
0
Not displayed if PB1H = 0.
0 denotes rate is always functional.
DB1
Enter the Current Dead Band value for Channel 1.
-36 to 36°F/-20 to 20°C
0
-20 to 20 Units
PB1C
Enter the Channel 1 Proportional Band value, Cooling.
0-900°F/0-500°C/0-500Units 45°F/25°C/25U
RS1C
Enter the Channel 1 Reset value, Cooling.
0.00 - 5.00 repeats/minute
0.00
Not displayed if PB1C = 0.
RT1C
Enter the Channel 1 Rate value, Cooling.
0.00 - 5.00 minutes
0.00
Not displayed if PB1C = 0.
CT1C
Enter the Channel 1 Cycle Time value, Cooling.
1 - 60 seconds
5
Not displayed if PB1C = 0. Dependent on output &OUT1.
RB1C
Enter the Channel 1 Rate Band value, Cooling.
0 - 7 times PB1C
0
Not displayed if PB1C = 0.
0 denotes rate is always functional.
RETURN Press the ENTER key to return to the SYSTEM prompt.
Press the MODE key to return to the PID prompt.
SETUP
Prompt
Description
Range
Default
Your Settings
ACCESS = (0) CALIB
To enter CALIB parameters use ACCESS (0) and ENTER.
TI XX:XX Read only. Displays the Real Time. HH:MM
HOUR
Enter the hours to display the system time-of-day clock.
0-23 hours
0
MIN
Enter the minutes to display the system time-of-day clock.
0-59 minutes
0
CAL1
Enter the Calibration Offset value for Channel 1.
-90 to 90°F/-50 to 50°C
0
-9.0 to 9.0°F/-5.0 to 5.0°C/U
CAL2
Enter the Calibration Offset value for Channel 2.
-90 to 90°F/-50 to 50°C
0
Dependent on TYP parameter.
-9.0 to 9.0°F/-5.0 to 5.0°C/U
A1H
Enter the Alarm 1 High value. Displayed if AUX1 = AL.
Dependent on AUX1 and ALTYP1 parameters.
See below.
A1L
Enter the Alarm 1 Low value. Displayed if AUX1 = AL.
Dependent on AUX1 and ALTYP1 parameters.
See below.
A2H
Enter the Alarm 2 High value. Displayed if AUX2 = AL.
Dependent on AUX2, ALTYP2, and TYP parameters.
See below.
A2L
Enter the Alarm 2 Low value. Displayed if AUX2 = AL.
Dependent on AUX2, ALTYP2, and TYP parameters.
See below.
RETURN Press the ENTER key to return to the SYSTEM prompt.
Press the MODE key to return to the CALIB prompt.
Make photocopies, keep original clean.
Range
Process Default
Deviation Default
Range
Process Default
Deviation Default
& High Slew Limit
& Low Slew Limit
AXH J
1382°F/750°C
999°F/555°C/U
AXL J
32°F/0°C
-999°F/-555°C/U
K
2282°F/1250°C
999°F/555°C/U
K
-328°F/-200°C/U
-999°F/-555°C/U
T
662°F/350°C
999°F/555°C/U
T
-328°F/-200°C
-999°F/-555°C/U
% RH
100%
555
% RH
0%
-555
RTD Whole
1112°F/600°C
999°F/555°C/U
RTD Whole
-328°F/-200°C
-999°F/-555°C/U
RTD Tenths
392.0°F/200.0°C
999°F/555°C/U
RTD Tenths
-99.9°F/-99.9°C
-999°F/-555°C/U
0 - 5 Whole
1985°F/1985°C
999°F/555°C/U
0 - 5 Whole
-117°F/-117°C
-999°F/-555°C/U
0 - 5 Tenths
198.5°F/198.5°C
999°F/555°C/U
0 - 5 Tenths
-11.7°F/-11.7°C
-999°F/-555°C/U
4 - 20 Whole
1985°F/1985°C
999°F/555°C/U
4 - 20 Whole
-285°F/-285°C
-999°F/-555°C/U
4 - 20 Tenths
198.5°F/198.5°C
999°F/555°C/U
4 - 20 Tenths -28.5°F/-28.5°C
-999°F/-555°C/U