WATLOW Series 922 User's Manual

How To Program the Series 922, Chapter 6

SETUP Menu

Allows the operator to select which parameter the analog retransmit
signal represents. For a chart recorder output, select C1 or C2. For a
remote set point signal (to slave controls) select SP1 or SP2. C2 and
SP2 will not appear if the TYP parameter is T or P. See SCALE
parameter below for further explanation. C1 = Channel 1 actual, C2 =
Channel 2 actual, SP1 = Set point channel 1, SP2 = Set point channel 2
Range: C1, C2, SP1, SP2

Default: C1

Allows the operator to scale the analog retransmit output for a certain
number of millivolts per least significant digit of the value. Reference 0
units = 0 volts.
Range: 1, 2, 5, 10mV

Default: 1

Represents the selection of the protocol type for serial communi-
cations. This selects XON/XOFF protocol or ANSI X3.28 communica-
tion protocol. This parameter will not appear if your Series 922 does
not have communications.
Range: XON or STX

Default: STX

Represents the baud rate that serial communications will be running at.
This parameter will not appear if your Series 922 does not have
communications.
Range: 1200, 2400, 4800, 9600

Default: 1200

Represents the device identification number as required for the ANSI
X3.28 communications protocol for the Series 922. This parameter will
not appear if COM has been selected as XON, or if your Series 922
does not have communications.
Range: 0 to 9

Default: 0

Allows for specific groups of parameters to be unaffected by the UP/
DOWN and ENTER keys, preventing these parameters from being
changed accidentally.
0 = No lock, full access of all parameters.
1 = Prevents user from editing all parameters except the SYSTEM
parameter group, the LOCK parameter, and the STEP and FILE
parameter in the PROGRAM and pre-run menus.
2 = Prevents user from editing all parameters except ER1, ER2, ALRM
in the SYSTEM menu, the LOCK parameter, and the STEP and FILE
parameter in the PROGRAM and pre-run menus.
Range: 0 to 2

Default: 0

Allows the operator to clear a file of the Series 922. Press ENTER, and
choose the FILE? that you want to clear.
Range: 1 to 10

From RETURN, you can go back to the SYSTEM prompt by pressing
the ENTER key, or return to SPCLFUNC by pressing the MODE key.

ANLG ( )

COM ( )

BAUD ( )

COM ID ( )

SCALE ( )

LOCK ( )

CLR FILE

RETURN