Specifications – Watlow Series 922 User Manual
Page 69
Appendix
69
WATLOW Series 922 User's Manual
Specifications
Output - Control Per Channel (Single or Dual)
•
Solid state relay, 0.5A @ 24VAC min. 264 VAC max., opto-isolated, zero
cross switching.
•
Solid state switch, 20mA @ 20VDC max, open collector switch-to-ground.
•
4-20mA into 600
Ω
load maximum.
Output/Input - Auxiliary
•
External, plug-in module.
•
Solid state relays, 2 or 8 ea., 0.5A @ 24VAC min. 264 VAC max.
•
Auxiliary supply: 21 to 33VDC, 25mA maximum.
•
Switched DC signal provides a minimum turn on voltage of 3VDC in a
minimum 500
Ω
load. Maximum on voltage not greater than 32VDC into an
infinite load.
Output - Analog Retransmit
•
Device driven must have an input impedance > 10k
Ω
.
•
Reference: 0 Units = 0 Volts.
•
Scalable: 1mV, 2mV, 5mV, or 10mV per LSD.
•
Maximum voltage Span: -9.5 to +9.5 volts.
Accuracy
•
Calibration Accuracy and Sensor Conformity:
±
0.15% of span,
±
1 digit at
77
°
F
±
5
°
F (25
°
C
±
3
°
C) ambient & rated line voltage
±
10%.
•
Accuracy Span: 1000
°
F or 540
°
C minimum.
•
Temperature Stability: 0.18
°
F/
°
F (0.1
°
C/
°
C) change in ambient.
•
Voltage Stability:
±
0.01% of span / % of rated line voltage.
Communications
•
Serial data communications.
•
RS-422A or RS-423A (RS-232C compatible).
•
Most operator indication and controls.
•
ANSI X3.28 protocol, or XON/XOFF protocol.
•
Isolated.
•
DB-9 Female connector.
Terminals
•
#6 compression type screw terminals.
Power
•
115/230VAC
±
10%, 50/60Hz
±
5%.
•
18VA maximum.
•
Data retention upon power failure via nonvolatile memory.
Operating Environment
•
32 to 130
°
F/0 to 55
°
C.
•
0 to 90% RH, non-condensing.
Dimensions
•
Height:
3.8 in.
(96.52 mm)
•
Width:
3.8 in.
(96.52 mm)
•
Overall depth:
7.0 in.
(177.80 mm)
•
Behind panel depth:
6.0 in.
(152.50 mm)
with connector for
communication and events:
8.8 in.
(223.52 mm)
•
Weight:
2.8 lb
(1.27 kg)