WATLOW Series 922 User's Manual

Starting Out, Chapter 1

DIP

Function

Normal

SW#

Operating

ON

OFF

Position

1

Cold Start

Warm Start

OFF

2

Display the factory selected Display all SPCLFUNC

Choose

SPCLFUNC parameters

parameters

3

Tenths of units displayed

No decimal displayed

Choose

4

0-5VDC/0-20mA input

1-5VDC/4-20mA input

Choose

5

Not Used

Not Used

OFF

6

Factory Test/Calibrate

Normal Operation

OFF

Changing the Position of a Switch

Whenever you change the position of a DIP switch, follow this procedure:

1.

Remove power from the Series 922. Turn the front panel screw 90° counter-
clockwise.

2.

Grip the front panel bezel and pull it straight out from the control case. The
control chassis will come out of the case as you pull the bezel.

3.

Set the DIP switch to the position you want.

4.

Return the control chassis to the case. Be sure you have it oriented
correctly. It will not fit in upside down, but check just the same. Press firmly,
but gently, to seat the chassis.

Control Chassis - Top View

DIP
Switches

DIP Switch #1 determines a warm or cold start. A "warm" start will save all
programmed information in the 922's memory backup. A "cold" start is a "clean"
startup condition; all user-programmed information is deleted. Your Series 922
leaves the factory programmed for a warm start. DIP Switch #2 selects whether
all SPCLFUNC parameters will be displayed or not. DIP Switch #3 determines
whether the decimal point will be displayed in tenths of units for 0-5V or 4-20mA
input and DIP Switch #4 is for 0-5VDC/0-20mA input or 1-5VDC/4-20mA input
selection. DIP Switch #5 is not used, and DIP Switch #6 is a factory test/cali-
brate switch.

Table 1 -
DIP Switch Selec-
tion.

Figure 3 -
DIP Switch Location
and Orientation.

DIP Switches

A007- 1727
Board

WARNING:
Doing a cold start
will cause all SETUP
parameters and files
to be lost. DO NOT
put DIP switch #1 in
the ON position
unless all user-
programmed
information is to be
cleared.

SPCLFUNC parame-
ters define the
personality of your
Series 922. Such as
input type, units of
measure, range,
calibration offset,
output action, alarm
type, and lock out.