Setup menu – Watlow Series 922 User Manual

Page 48

background image

48

WATLOW Series 922 User's Manual

How To Program the Series 922, Chapter 6

Make photocopies, keep original clean.

Prompt

Description

Range

Default

Your Settings

ACCESS = (5) SPCLFUNC
To enter SPCLFUNC parameter, use ACCESS (5) and press ENTER.
C/F/U

Enter the unit of measure code. (Celcius/Fahrenheit/Units)

C/F/U

F

Not displayed if DIP Switch #2 is ON.

TYP

Enter actual process display to be shown.
Temperature/Process/Humidity

Dual T/C

T T or T

T T

Dual RTD

T T or T H or T

T T

Dual RTD 0.1

T T or T H or T

T T

0.1 RTD, Process

T P or T V or T

T P

T/C, Process

T P or T V or T

T P

RTD, Process

T P or T V or T

T P

Dual Process

P P or P V or P

P P

Not displayed if DIP Switch #2 is ON.

OUT1

Enter the control output for Channel 1, Outputs 1 and 2.

Heat PID/Cool PID

HTCL

HTCL

Cool PID/Heat PID

CLHT

Not displayed if DIP Switch #2 is ON.

OUT2

Enter the control output for Channel 2, Outputs 3 and 4.

Heat PID/Cool PID

HTCL

HTCL

Cool PID/Heat PID

CLHT

Not displayed if DIP Switch #2 is ON. Dependent on TYP.

R1L

Enter the Range Low value for Channel 1.

Dependent on input selection.

Not displayed is DIP Switch #2 is ON.

See your TYP parameter setting.

R1H

Enter the Range High value for Channel 1.

Dependent on input selection.

Not displayed if DIP Switch #2 is ON.

See your TYP parameter setting.

R2L

Enter the Range Low value for Channel 2.

Dependent on input selection.

Not displayed if DIP Switch #2 is ON. Dependent on TYP.

See your TYP parameter setting.

R2H

Enter the Range High value for Channel 2.

Dependent on input selection.

Not displayed if DIP Switch #2 is ON. Dependent on TYP.

See your TYP parameter setting.

AUX1

Enter the Auxiliary Output 1.

AUX1 AL

Alarm output

AL

AUX 1 EV

Event output

Not displayed if DIP Switch #2 is ON. Dependent on event board.

AUX2

Enter the Auxiliary Output 2.

AUX2 AL

Alarm output

AL

AUX2 EV

Event output

Not displayed if DIP Switch #2 is ON. Dependent on TYP & event board.

ALTYP1

Enter Alarm Type 1.

ALTYP1 P

Process alarm

P

ALTYP1 D

Deviation alarm

Not displayed if DIP Switch #2 is ON. Dependent on AUX1 & event board.

ALTYP2

Enter Alarm Type 2.

ALTYP2 P

Process alarm

P

ALTYP2 D

Deviation alarm

Not displayed if DIP Switch #2 is ON Dependent on AUX2, TYP & event board.

LAT

Enter the Alarm function type.

LAT or NLAT

NLAT

Not displayed if DIP Switch #2 is ON.

RTD

Enter input gain of RTD input channels for different curves.

JIS or DIN

JIS

Not displayed if DIP Switch #2 is ON. Dependent on input.

ALT

Set altitude in feet for humidity mode.

0, 2500, 5000

0

Not displayed if DIP Switch #2 is ON. Dependent on input.

GS

Enter the Guaranteed Soak.

0 - 50°C

0

ANLG

Enter parameter the Analog retransmit signal represents.

C1, C2, SP1, SP2

C1

SCALE

Enter millivolts to scale analog retransmit output.

1, 2, 5, 10

1

COM

Select between XON/XOFF or ANSI X3.28 protocol.

XON or STX

STX

Dependent on communications capability.

BAUD

Select baud rate for serial communications to run at.

1200, 2400,

1200

Dependent on communications capability.

4800, 9600

COM ID

Enter the Communications protocol Identification.

0 - 9

0

Dependent on communications capability and COM = STX.

LOCK

Enter the Front panel Lock code.

0 - 2

0

CLR FILE

Press ENTER to display FILE?. Enter a file number to clear.

1 - 10

1

RETURN

Press the ENTER key to return to the SYSTEM prompt.
Press the MODE key to return to the SPCLFUNC prompt.

SETUP Menu

Table 9 continued

NOTE: Changing these parameter
values will default other parameters
and clear all files. See Page 53 & 54