Setup menu – Watlow Series 922 User Manual
Page 48
48
WATLOW Series 922 User's Manual
How To Program the Series 922, Chapter 6
Make photocopies, keep original clean.
Prompt
Description
Range
Default
Your Settings
ACCESS = (5) SPCLFUNC
To enter SPCLFUNC parameter, use ACCESS (5) and press ENTER.
C/F/U
Enter the unit of measure code. (Celcius/Fahrenheit/Units)
C/F/U
F
Not displayed if DIP Switch #2 is ON.
TYP
Enter actual process display to be shown.
Temperature/Process/Humidity
Dual T/C
T T or T
T T
Dual RTD
T T or T H or T
T T
Dual RTD 0.1
T T or T H or T
T T
0.1 RTD, Process
T P or T V or T
T P
T/C, Process
T P or T V or T
T P
RTD, Process
T P or T V or T
T P
Dual Process
P P or P V or P
P P
Not displayed if DIP Switch #2 is ON.
OUT1
Enter the control output for Channel 1, Outputs 1 and 2.
Heat PID/Cool PID
HTCL
HTCL
Cool PID/Heat PID
CLHT
Not displayed if DIP Switch #2 is ON.
OUT2
Enter the control output for Channel 2, Outputs 3 and 4.
Heat PID/Cool PID
HTCL
HTCL
Cool PID/Heat PID
CLHT
Not displayed if DIP Switch #2 is ON. Dependent on TYP.
R1L
Enter the Range Low value for Channel 1.
Dependent on input selection.
Not displayed is DIP Switch #2 is ON.
See your TYP parameter setting.
R1H
Enter the Range High value for Channel 1.
Dependent on input selection.
Not displayed if DIP Switch #2 is ON.
See your TYP parameter setting.
R2L
Enter the Range Low value for Channel 2.
Dependent on input selection.
Not displayed if DIP Switch #2 is ON. Dependent on TYP.
See your TYP parameter setting.
R2H
Enter the Range High value for Channel 2.
Dependent on input selection.
Not displayed if DIP Switch #2 is ON. Dependent on TYP.
See your TYP parameter setting.
AUX1
Enter the Auxiliary Output 1.
AUX1 AL
Alarm output
AL
AUX 1 EV
Event output
Not displayed if DIP Switch #2 is ON. Dependent on event board.
AUX2
Enter the Auxiliary Output 2.
AUX2 AL
Alarm output
AL
AUX2 EV
Event output
Not displayed if DIP Switch #2 is ON. Dependent on TYP & event board.
ALTYP1
Enter Alarm Type 1.
ALTYP1 P
Process alarm
P
ALTYP1 D
Deviation alarm
Not displayed if DIP Switch #2 is ON. Dependent on AUX1 & event board.
ALTYP2
Enter Alarm Type 2.
ALTYP2 P
Process alarm
P
ALTYP2 D
Deviation alarm
Not displayed if DIP Switch #2 is ON Dependent on AUX2, TYP & event board.
LAT
Enter the Alarm function type.
LAT or NLAT
NLAT
Not displayed if DIP Switch #2 is ON.
RTD
Enter input gain of RTD input channels for different curves.
JIS or DIN
JIS
Not displayed if DIP Switch #2 is ON. Dependent on input.
ALT
Set altitude in feet for humidity mode.
0, 2500, 5000
0
Not displayed if DIP Switch #2 is ON. Dependent on input.
GS
Enter the Guaranteed Soak.
0 - 50°C
0
ANLG
Enter parameter the Analog retransmit signal represents.
C1, C2, SP1, SP2
C1
SCALE
Enter millivolts to scale analog retransmit output.
1, 2, 5, 10
1
COM
Select between XON/XOFF or ANSI X3.28 protocol.
XON or STX
STX
Dependent on communications capability.
BAUD
Select baud rate for serial communications to run at.
1200, 2400,
1200
Dependent on communications capability.
4800, 9600
COM ID
Enter the Communications protocol Identification.
0 - 9
0
Dependent on communications capability and COM = STX.
LOCK
Enter the Front panel Lock code.
0 - 2
0
CLR FILE
Press ENTER to display FILE?. Enter a file number to clear.
1 - 10
1
RETURN
Press the ENTER key to return to the SYSTEM prompt.
Press the MODE key to return to the SPCLFUNC prompt.
SETUP Menu
Table 9 continued
NOTE: Changing these parameter
values will default other parameters
and clear all files. See Page 53 & 54
for details.