WATLOW Series 922 User's Manual

Appendix

Specifications

Specifications

Control Mode

Microprocessor-based, user selectable modes.

Dual inputs, dual control outputs per channel.

8 event outputs/1 event input/1 remote hold input.

99 step programmer with up to 10 profiles.

Control outputs: User selectable as: Heat/Cool, Cool/Heat.

Outputs independent, or related via deadband for Heat/Cool.

ON/OFF: 3

°

F or 1.7

°

C switching hysteresis or 0.3

°

F or 0.17

°

C for 0.1

°

Units .

PID parameters per channel:
Proportional band: 0 to 500

°

C or 0 to 50.0

°

C for 0.1

°

Units.

Reset: 0.00 to 5.00 repeats per minute.
Rate: 0.00 to 5.00 minutes.
Rate band: 0 to 7 times proportional band.
Cycle time: 1 to 60 seconds.

Deadband:

±

36

°

F,

±

20

°

C or Units

±

2.0

°

C for 0.1

°

Units.

Auxiliary outputs: User selectable as:

• Events 1 & 2 selectable as alarms for Channels 1 & 2.
• Process or deviation value, per output.
• Alarms, latching or non-latching. When non-latching, control will have

3

°

F/1.7

°

C switching hysteresis or 0.3

°

F/0.17

°

C for 0.1

°

Units.

• Separate high and low values, per output.

Operator Interface

Membrane front panel.

Four digit 1/2" LEDs displaying actual process input value.

LED indication of

°

C,

°

F, or process variable units.

MODE, ENTER, UP, DOWN, and RUN/HOLD keys.

Eight character alphanumeric display of operating data.

Input

Thermocouple, RTD and electrical process input.

Automatic cold junction compensation for thermocouple.

RTD input 2 or 3 wire, platinum, 100 ohm @ 0

°

C, calibrated to JIS curve

#3916 (0.003916

/

/

°

C), DIN curve #3850 (0.003850

/

/

°

C).

Sensor break protection de-energizes control outputs to protect system.

Ungrounded sensors required..

Operating ranges user selectable.

J t/c:

32 to 1382

°

F

or

0

to

750

°

C

K t/c:

-328 to 2282

°

F

or -200

to 1250

°

C

T t/c:

-328 to

662

°

F

or -200

to

350

°

C

1

°

RTD:

-328 to 1112

°

F

or -200

to

600

°

C

0.1

°

RTD: -99.9 to 392.0

°

F

or -99.9

to 200.0

°

C

0-5VDC:

-99 to 1800 units

4-20mA:

-99 to 1800 units

RH, 0-5VDC: 0 to 100% RH Vaisala sensor

Calibration offset or input signal,

±

90

°

F,

±

50

°

C,

±

50 PVU's, front panel

adjustable 9.0

°

F,

±

5.0

°

C for 0.1

°

C Units.

°

F,

°

C, or process variable units are user selectable.