Setup menu – Watlow Series 922 User Manual
Page 55
How To Program the Series 922, Chapter 6
55
WATLOW Series 922 User's Manual
SETUP Menu
This parameter determines whether Auxiliary Output 1 will be an
alarm or event output for the Series 922. This parameter will not appear if the 2
event or 8 event output board is not connected, or DIP Switch #2 is ON.
Range:
Alpha Display
Auxiliary Output 1's Function
AUX1 AL
Alarm Output defined for Event 1
AUX1 EV
Event Output defined for Event 1
Default: AL
This parameter determines whether Auxiliary Output 2 will be an alarm or event
output for the Series 922. This parameter will not appear if: the external 2 event
or 8 event output board is not connected; the TYP parameter has been set to
"T" or "P" (Channel 1 only), or DIP Switch #2 is ON.
Range:
Alpha Display
Auxilary Output 2's Function
AUX2 AL
Alarm Output defined for Event 2
AUX2 EV
Event Output defined for Event 2
Default: AL
Determines whether the alarm type for Auxiliary Output 1 will be a process alarm
or a deviation alarm for the Series 922. This parameter will not appear if: The 2
or 8 event output board is not connected; AUX1 = EV; or DIP Switch #2 is ON.
Range:
Alpha Display
Alarm Type
ALTYP1 P
Process Alarm
ALTYP1 D
Deviation Alarm
Default: P
Determines whether the alarm type for Auxiliary Output 2 will be a process alarm
or deviation alarm. This parameter will not appear if: The external 2 event or 8
event output board is not connected; if the TYP parameter has been set to "T"
or "P" (Channel 1 only), or if DIP Switch #2 is ON.
Range:
Alpha Display
Alarm Type
ALTYP2 P
Process Alarm
ALTYP2 D
Deviation Alarm
Default: P
Selects alarms as latching or non-latching. Latching means the alarms remain
active until you manually clear it. This will not appear if DIP Switch #2 is ON.
Range: LAT or NLAT
Default: NLAT
Allows the operator to change the input gain of one or both of the RTD input
channels for different curves. This parameter will not appear if: The input board
type is Dual T/C, T/C Process, or Dual Process, or DIP Switch #2 is ON.
Range: JIS or DIN
Default: JIS
The Altitude parameter represents the setting for altitude in feet above sea level
for barometric correction when in the humidity mode. This parameter only
appears if the TYP parameter is set to T/H. This parameter will not appear if DIP
Switch #2 is ON.
Range: 0, 2500, 5000
Default: 0
The Guaranteed Soak parameter guarantees the actual temperature for Channel
1 is being controlled within a window around set point while a profile is running.
If exceeded, the step time clock stops until the actual temperature is within the
soak window. 0 = Guaranteed Soak is not active; >0 = Guaranteed Soak
Window (active). Only applies to Channel 1.
Range: 0 to 90
°
F / 0 to 50
°
C / 0 to 50 Units; 0 to 9.0
°
F / 0 to 5.0
°
C /
0 to 5.0 Units
Default: 0
GS
( )
ALT ( )
RTD ( )
LAT ( )
ALTYP2 ( )
ALTYP1 ( )
AUX2 ( )
AUX1 ( )