beautypg.com

Connecting the power cord – Proface GP4100 - 3.4 Compact HMIs" User Manual

Page 56

background image

Chapter 4 Installation and Wiring

4-11

„Connecting the Power Cord

(1)

Confirm that the power cord is unplugged from the power supply.

(2)

Check the rated voltage, and remove the sticker on the power connector that reads "DC 24V".

(3)

Remove the power connector (plug) from the main unit.

(4)

Strip the membrane of the power cord, and connect them to the Power Connector.

(5)

Reattach the Power Connector (plug).

• Be sure to remove the connector from the GP unit prior to starting wiring. Failure to

do so may cause an electric shock.

• The temperature rating of field installed Conductors:75

o

C only.

• Use a flat-blade screwdriver (Size 0.4 x 2.5 mm (0.015 to 0.098 in.)) to tighten the

terminal screws.

The torque required to tighten these screws is 0.22 to 0.25N

•m[1.95 to 2.2Lb•In.].

• Do not solder the cable connection. Doing so may damage the unit due to abnormal

heat or cause a fire.

Be sure to twist the power cords together, up to the power connector.

Power
Connector
(Socket)

Rear

Power Connector (Plug)

(GP4104)

FG

+