beautypg.com

Installation requirements – Proface GP4100 - 3.4 Compact HMIs" User Manual

Page 48

background image

Chapter 4 Installation and Wiring

4-3

„Installation Requirements

For easier maintenance, operation, and improved ventilation, be sure to install the GP at least 100 mm

[3.94 in.] away from adjacent structures and otherequipment.

Be sure that the surrounding air temperature and the ambient humidity are within their designated ranges.

(Surrounding air temperature: 0 to 50°C, Ambient humidity: 10 to 90%RH, Wet bulb temperature: 39°C

max.) When installing the GP on the panel of a cabinet or enclosure, "Surrounding air temperature"

indicates both the panel face and cabinet or enclosure’s internal temperature.

Be sure that heat from surrounding equipment does not cause the GP to exceed its standard operating

temperature.

100[3.94]

Unit: mm[in.]

100[3.94]

100[3.94]

100[3.94]

100[3.94]

100
[3.94]

100
[3.94]

Panel
Face

Cabinet
interior