EZCT-2000C USER’S MANUAL

REV 1

100

4.6

Disabling the H Voltage Checking Feature

The EZCT-2000C's H Voltage input can only handle voltage up to 100 Vac. When a saturation
test is being performed, the unit monitors the H voltage and stops the saturation test if a
voltage above 100 Vac is detected. In certain noisy substation environments, the unit may pick
up a noise spike which may be interpreted as high voltage input to the H terminal, causing the
unit to stop the saturation test. For such cases, it may be necessary to disable the H Voltage
monitoring feature so that a saturation test can be properly completed. Follow the steps below
to disable the H Voltage checking features:

WARNING

If this feature is disabled and an actual over-voltage situation exists (voltage over
100 Vac), it will NOT be detected by the EZCT-2000C and can cause damage to the
unit. This feature should be disabled only after confirming that an actual over-
voltage situation does not exist.

a. Start from the "START-UP" menu:

Press the

[2]

key (SETUP).

b. The following screen will be displayed:

Press the

[6]

key (NEXT PAGE).

c. The following screen will be displayed:

Press the

[6]

key (DISABLE H-VTG CHECK).

1.

SET TIME

2.

SET LANGUAGE

3.

BURIED CT IN DELTA

4.

KNEE POINT MARKER

5.

PRINT RAW DATA

6.

DISABLE H-VTG CHECK

1.

RECORD ID

2.

PRINT RECORD

3.

RECORD DIRECTORY

4.

SAVE/RES RECORD

5.

ERASE RECORD

6. NEXT PAGE

1.

RUN TEST 05/07/13

2.

SETUP 08:18:28

3.

TEST PLANS

4.

DIAGNOSTICS

5.

CURRENT SOURCE