FUNCTION GROUP 8

MULTI-FUNCTION OUTPUT RELAYS AND OUTPUT SIGNAL OPERATION

Function

No. Description

Range/Code

Factory

Setting

Actual

Setting

8.00 *

Multi-Function Output
Relay 1
(Terminals 23 – 25)

0000

8.01 *

Multi-Function Output
Relay 2
(Terminals 26 – 28)

0001

8.02 *

Multi-Function Open
Collector Output 1
(Terminals 11, 12)

0002

8.03 *

Multi-Function Open
Collector Output 2
(Terminals 13, 14)

0000: Run

0001: Fault

1

0002: Target Frequency
(8.04

±

8.05)

0003: Frequency Threshold Level
(> 8.04 – 8.05)

2

0004: Frequency Threshold Level
(< 8.04 + 8.05)

3

0005: I

2

t or I•t Fault

0006: Load Loss (See 5.03)

0007: External Fault

0008: Motor Overload

4

0004

8.04

Frequency Set Point
(Hz)

0.00 – 240.0

0.00

8.05

Frequency Bandwidth
(± Hz)

0.00 – 30. 00

1.00

8.06

Analog Output 1 Mode
(Terms. 15, 16)
(0 – 5 VDC)

0000: Motor Frequency
0001: Set Frequency
0002: Motor Voltage
0003: Bus Voltage
0004: Motor Current

0000

8.07

Analog Output 1 Gain
(%)

0 – 200

100

8.08

Analog Output 2 Mode
(Terms. 17, 18)
(See 8.09)

0000: Motor Frequency
0001: Set Frequency
0002: Motor Voltage
0003: Bus Voltage
0004: Motor Current

0000

8.09

Analog Output 2 Type

(5)

0000: 0 – 5 VDC
0001: 0 – 20 mA DC
0002: 4 – 20 mA DC

0000

8.10

Analog Output 2 Gain
(%)

0 – 200

100

Notes: 1. The Output Relay contacts will change state due to all Faults and Recovered
Faults. 2. The relay will activate above the setting in Function No. 8.04 and deactivate below
the setting in Function No. 8.04 minus the setting in Function No. 8.05. 3. The relay will
activate below the setting in Function No. 8.04 and deactivate above the setting in Function
No. 8.04 plus the setting in Function No. 8.05. 4. The Output Relay will change state when
the I

2

t or I•t Timer starts. 5. Analog Output 2 Type: For 0 – 5 VDC (code "0000"), set

Jumpers J2 and J3, on the IODA, to the "VOLT" position (factory setting). For 0 – 20 mA DC
(code "0001") or 4 – 20 mA DC (code "0002"), set Jumpers J2 and J3, on the IODA, to the
"CUR" position.

*Functions which can only be changed while the drive is in Stop Mode.