TABLE 23
MULTI-FUNCTION OUTPUT RELAY CONTACTS PROGRAMMING
Function No.
Code
8.00: Multi-Function Output Relay 1
0000: Run
0001: Fault
0002: Target Frequency
0003: Frequency Threshold Level (> 8.04 – 8.05)
0004: Frequency Threshold Level (< 8.04 + 8.05)
0005: I
2
t or I•t Fault
0006: Load Loss
0007: External Fault
0008: Motor Overload
8.01: Multi-Function Output Relay 2
0000: Run
0001: Fault
0002: Target Frequency
0003: Frequency Threshold Level (> 8.04 – 8.05)
0004: Frequency Threshold Level (< 8.04 + 8.05)
0005: I
2
t or I•t Fault
0006: Load Loss
0007: External Fault
0008: Motor Overload
4.11 MULTI-FUNCTION OPEN COLLECTOR OUTPUTS
Two Open Collector Outputs are provided, which can be programmed for Run,
Fault, Target Frequency, Frequency Threshold Level (> 8.04 – 8.05), Frequency
Threshold Level (< 8.04 + 8.05), I
2
t or I•t Fault, Load Loss, External Fault, and
Motor Overload. See Figure 30, on page 38, for connections. See Table 24, on
page 38, for drive programming. See Table 25, on page 38, for the Multi-
Function Open Collector Output Electrical Ratings. See Figure 31, on page 39,
for a typical application for the Open Collector Output.
Multi-Function Open Collector Output "1": Factory programmed to operate as
a Target Frequency indicator (Function No. 8.02 set to "0002" (factory setting)).
TB1 Terminal "11" is the Collector and Terminal "12" is the Emitter (internal
circuit common).
Multi-Function Open Collector Output "2": Factory programmed to operate as
a Frequency Threshold Level (< 8.04 + 8.05) indicator (Function No. 8.03 set to
"0004" (factory setting)). TB1 Terminal "13" is the Collector and Terminal "14" is
the Emitter (internal circuit common).