APPLICATION NOTES FOR AUTO/MANUAL START MODE (FUNCTION NO. 1.05)
After the Extenal Fault has been Cleared:
1. If the drive is set for Manual Start Mode ("0000" (factory setting)), Manual Start
with Ride-Through ("0001"), or Auto Start After Undervoltage Fault Clears
("0002"), it will have to be manually restarted after the external fault has been
cleared. Use the Reset Key on the Keypad or the external Reset Switch or
Contact to restart the drive.
2. If the drive is set for Auto Start All Faults (Except Short circuit Fault) ("0003"), it will
automatically restart after the external fault has been cleared, for the number of
restart attempts set in Function No. 1.07 (factory set to 3). After which, the drive
will have to be restarted using the Reset Key on the Keypad or the external Reset
Switch or Contact.
3. If the drive is set for Auto Start All Faults (Except 1
2
t, I•t, and Short Circuit Faults)
("0004"), it will automatically restart after the external fault has been cleared.
CAUTION! External Fault is not to be used as an Emergency Stop or safety
disconnect since it is not fail-safe. Use only the AC line for this purpose.
FIGURE 18
EXTERNAL FAULT CONNECTIONS
*Optional.
TABLE 12
EXTERNAL FAULT PROGRAMMING
Function No.
Code
7.03: Multi-Function Input Terminal 4
0009: Reset*
7.04: Multi-Function Input Terminal 5
0008: External Fault (N.O. Contact)
0012: External Fault (N.C. Contact)
*Factory setting.