TABLE 20
REMOTE UNIDIRECTIONAL MAIN SPEED POTENTIOMETER PROGRAMMING
Function No.
Code
1.00: Run/Stop-Forward/Reverse Control
0001: External Contacts
2.00: Frequency Control
0002: Analog Signal 1
7.04: Multi-Function Input Terminal 5
0010: N.O. Start*
*Factory setting.
BIDIRECTIONAL OPERATION WITH START/STOP
(Use Analog Input "1" Only)
Connect the Main Speed Potentiometer to Terminals "9" (+5 Volts), "19" (Analog
Input 1), and "10" (-5 Volts). Connect the Start/Stop Switch or Contact to
Terminal "5", which is factory set for N.O. Start ("0010"), and to any available
common terminal ("8", "12", "14", "16", "18" "20", "22"). See Figure 27 for
connections. See Table 21 for drive programming.
Operation: Close the Start/Stop Switch or contact to start the drive. At 50%
rotation, the Main Speed Potentiometer is set for zero speed. Rotating the Main
Speed Potentiometer clockwise will increase motor frequency in the forward
direction. Rotating the Main Speed Potentiometer counterclockwise will increase
motor frequency in the reverse direction. Open the Start/Stop Switch or Contact
to stop the drive.
FIGURE 27
REMOTE BIDIRECTIONAL MAIN SPEED POTENTIOMETER CONNECTIONS
*Use a jumper, between Terminals "5" and "8", if a Start/Stop Switch or Contact is not
required.
TABLE 21
REMOTE BIDIRECTIONAL MAIN SPEED POTENTIOMETER PROGRAMMING
Function No.
Code
1.00: Run/Stop-Forward/Reverse Control
0001: External Contacts
2.00: Frequency Control 0002:
Analog Signal 1
7.04: Multi-Function Input Terminal 5
0010: N.O. Start*
9.03: Analog Input 1 Type
0001: Bidirectional
*Factory setting.