TABLE 7

BIDIRECTIONAL PRESET FREQUENCY SELECTION PROGRAMMING

Function No.

Code/Range

1.00: Run/Stop-Forward/Reverse Control 0001:

External Contacts

3.00: Stored Set Frequency 00.00

Hz

7.00: Multi-Function Input Terminal 1 0000:

Preset Frequency Operation*

7.01: Multi-Function Input Terminal 2 0001:

Preset Frequency Operation*

7.02: Multi-Function Input Terminal 3 0002:

Preset Frequency Operation*

7.04: Multi-Function Input Terminal 5 0010:

N.O. Start*

7.05: Multi-Function Input Terminal 6 0006:

Forward/Stop Command

7.06: Multi-Function Input Terminal 7 0007:

Reverse/Stop Command

*Factory setting.



4.2 UP/DOWN FREQUENCY COMMAND

The Multi-Function Input Terminals can be used for remote Up/Down Frequency
Control in lieu of the Keypad. See Figures 14 and 15, on pages 20 and 22.


Connect the Up and Down Switches or Contacts to Multi-Function Input
Terminals "6" and "7", which are factory set for Up and Down Frequency
Command ("0003" and "0004"). The common of the switches or contacts can be
connected to any available common terminal ("8", "12", "14", "16", "18", "20",
"22").

Notes: 1. The drive is factory set for Unidirectional (Forward) Operation. For
Bidirectional Operation, use two Multi-Function Inputs for Forward/Stop and
Reverse/Stop, as described in Section 4.2.2, on page 21. 2. If a Multi-Function
Input Terminal is programmed for Reverse/Stop Command ("0007"), when
activated, the drive will remain "locked" in Reverse Operation until two Multi-
Function Input Terminals are programmed for Forward/Stop Command ("0006")
and Reverse/Stop Command ("0007").

Application Notes: 1. The Up/down Frequency Command Operation can be
programmed for "Free-Running" or "Incremental" frequency change by setting
Up/Down Frequency Control Mode (Function No. 7.14) for "Free Running"
("0000" (factory setting)) or "Incremental Change" ("0001"). 2. In "Free Running"
Mode, the rate of change of the “Up” control is proportional to the Accel Time
(Function No. 3.03) and the rate of change of the “Down” control is proportional
to the Decel Time (Function No. 3.04). 3. In "Incremental Change" Mode, the
step of change of the "Up" or "Down" control is set by Function No. 7.15 (range is
0.01 – 30.00 Hz (factory set to 1.00 Hz)).

4.2.1 UNIDIRECTIONAL UP/DOWN FREQUENCY CONTROL

See Figure 14, on page 20, for connections. See Table 8, on page 21, for
drive programming.

Connect the Start/Stop Switch or Contact to Multi-Function Input Terminal
"5", which is factory set for N.O. Start ("0010"). The common of the switch
or contact can be connected to any available common terminal ("8", "12",
"14", "16", "18", "20", "22").