KB Electronics IODA, Input/Output Module for use with all KBDA/KBMK Controls User Manual
Page 14
14
TABLE 1
TERMINAL BLOCK TB1 WIRE AND TIGHTENING TORQUE SPECIFICATIONS
Maximum Wire Size (Cu)
Recommended Tightening Torque
AWG
mm
2
lbs-in
kg-cm
16 1.3 6 7
TABLE 2
FUNCTIONS, FEATURES, AND TERMINAL ASSIGNMENT
Terminal Assignment
Multi-Function Input Terminals
1
(Digital Inputs)
Power
Supply
2
Multi-
Function
Outputs
2
Analog
Outputs
2
Analog
Inputs
2
Relay
Outputs
3
1 – 7
0000: Preset Frequency Operation
1
0001: Preset Frequency Operation
1
0002: Preset Frequency Operation
1
0003: Up Frequency Command
(See
Function
No.
7.14)
0004: Down Frequency Command
(See
Function
No.
7.14)
0005: Accel/Decel 2
(See
Function
No.
7.16)
0006: Forward/Stop Command
0007: Reverse/Stop Command
0008: External Fault
(N.O.
Contact)
0009: Reset
0010: N.O. Start
(2-Wire or 3-Wire Start/Stop)
0011: N.C. Stop
(3-Wire
Start/Stop)
Mul
ti
-Functi
on
Input Ter
m
in
al
C
odes (Functi
on Gr
oup
7)
0012: External Fault
(N.C.
Contact)
8
Common
9
+5 Volts
10
-5 Volts
11
Open
Collector 1
12
Common
13
Open
Collector 2
14
Common
15
Analog
Output 1
16
Common
17
Analog
Output 2
18
Common
19
Analog
Input 1
20
Common
21
Analog
Input 2
22
Common
23
RY1
N.O.
24
RY1
Common
25
RY1
N.C.
26
RY2
N.O.
27
RY2
Common
28
RY2
N.C.
Notes: 1. Multi-Function Input Terminals "1" – "7" can be programmed for: 7 Preset
Frequencies*, Up/Down Frequency Command, Accel/Decel 2, Forward/Stop, Reverse/Stop,
External Fault, Reset, and 2-Wire/3-Wire Start/Stop. 2. Common Terminals "8", "12", "14",
"16", "18", "20", "22" are all internally wired together and can be used with any of the Multi-
Function Input Terminals "1" – "7". 3. RY1 Common (Terminal "24") is the contact common
only for Relay 1. RY2 Common (Terminal "27") is the contact common only for Relay 2.
*The 7 Preset Frequencies are obtained using a combination of Terminals
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3.