KB Electronics IODA, Input/Output Module for use with all KBDA/KBMK Controls User Manual
Page 22
22
FIGURE 15
BIDIRECTIONAL UP/DOWN FREQUENCY CONTROL CONNECTIONS
TABLE 9
BIDIRECTIONAL UP/DOWN FREQUENCY CONTROL PROGRAMMING
Function No.
Code/Range
1.00: Run/Stop-Forward/Reverse Control
0001: External Contacts
2.00: Frequency Control
0005: Up/Down Using MFITs
7.02: Multi-Function Input Terminal 3 0006:
Forward/Stop Command
7.03: Multi-Function Input Terminal 4 0007:
Reverse/Stop Command
7.04: Multi-Function Input Terminal 5
0010: N.O. Start*
7.05: Multi-Function Input Terminal 6 0003:
Up Frequency Command*
7.06: Multi-Function Input Terminal 7 0004:
Down Frequency Command*
7.14: Up/Down Frequency Control Mode 0000: Free-Running 0001: Incremental
7.15: Increment of Up/Down Frequency**
0.01 – 30.00 Hz: Set to Desired Frequency
*Factory setting.
**Use with Function No. 7.14 code "0001" only.
4.3 ACCEL/DECEL
"2"
The drive provides a secondary Accel/Decel Time setting, which can be remotely
selected with a normally open switch or contact connected to a Multi-Function
Input Terminal. See Figure 16, on page 23, for connections. See Table 10, on
page 23, for drive programming.
Connect the Accel/Decel 2 Switch or Contact to any Multi-Function Input
Terminal "1" – "7". Terminal "6" has been arbitrarily chosen for Accel/Decel 2.
Connect the common of the switch or contact to any available common terminal
("8", "12", 14", "16", "18", "20", "22").
Operation: When the Accel/Decel 2 Switch or Contact is closed, the Accel/Decel
2 setting is selected. When the Accel/Decel 2 Switch or Contact opened, the
drive reverts to the Accel/Decel settings in Function Nos. 3.03 and 3.04.
Accel/Decel 2 overrides the Accel and Decel settings in Function Nos. 3.03 and
3.04.