KB Electronics IODA, Input/Output Module for use with all KBDA/KBMK Controls User Manual
Page 15
15
TABLE 3
MULTI-FUNCTION INPUT TERMINAL, FUNCTION NO., AND CODE ASSIGNMENT
MFIT
1 2 3 4 5 6 7
Function No.
7.00 7.01 7.02 7.03 7.04 7.05 7.06
Factory Code
Setting
0000 0001 0002 0009 0010 0003 0004
Code
Description
Preset
Frequency
Operation
Preset
Frequency
Operation
Preset
Frequency
Operation
Reset
2-Wire
N.O.
Start/Stop
Up
Frequency
Command
Down
Frequency
Command
Each Multi-Function Input Terminal is controlled by a specific Function No.
Although factory set to a specific code, they can also be reprogrammed to any Function
Code "0000" – "0012" listed in Table 2, on page 14. Also see Function Group 7, on page 41.
4.1 PRESET
FREQUENCIES
The drive is factory programmed for 7 Preset Frequencies, which can be selected
using remote switches or contacts connected to Multi-Function Input Terminals
"1" – "3". See Figures 11 and 12, on page 17. See Table 4 for the terminals to
select for the preset frequencies.
The 7 Preset Frequencies are obtained using a combination of Multi-Function
Input Terminals 1, 2, 1+2, 3, 1+3, 2+3, 1+2+3. The Preset Frequencies can be
changed from their factory settings by reprogramming Function Nos. 7.07 – 7.13.
8
th
Preset Frequency: If none of the Multi-Function Input Terminals are activated,
the drive will operate at the Stored Set Frequency (Function No. 3.00) of 5.00 Hz.
If the 8
th
Preset Frequency is not required, set Function No. 3.00 to 00.00 Hz.
Note: For Preset Frequency Operation only, the drive does not have to be
reprogrammed for External Contacts Operation. Multi-Function Input Terminals
"1" – "3" are factory set to codes "0000", "0001", and "0002", which automatically
sets the drive for Preset Frequency Operation.
Application Notes: 1. The drive is factory set for Unidirectional (Forward)
Operation. For Bidirectional Operation, use two Multi-Function Inputs for
Forward/Stop and Reverse/Stop, as described in Section 4.1.2, on page 18.
2. Be sure to program both Forward/Stop and Reverse/Stop Operation (codes
"0006" and "0007"). If only one direction is programmed, the drive will remain
"locked" in that direction.
TABLE 4
PRESET FREQUENCY SELECTION
Multi-Function Input Terminals to Select
Preset Frequency
Terminal 1
Terminal 2
Terminal 3
Function No. 7.00
Set to "0000"*
Function No. 7.01
Set to "0001"*
Function No. 7.02
Set to "0002"* No. Function No.
Hz
(Factory Setting)
●
1
7.07
5.00
●
2
7.08
10.00
●
●
3
7.09
20.00
● 4
7.10 25.00
●
● 5
7.11 30.00
●
● 6
7.12 35.00
●
●
● 7
7.13 40.00
*Factory setting.