X76ctm system wiring information, Hazardous location non hazardous location, X76ctm-4x tank monitor – Ronan X76CTM User Manual
Page 28
27
LS-3
N.O. OR N.C.
CONTACTS
LS-7
N.C.
CONTACTS
JT-2P
JT-2V
N.O. OR N.C.
CONTACTS
LS-30
N.C.
CONTACT
N.O.
CONTACT
TYPICAL CONTACT SENSORS
950xxxB OR 951xxxB PROBE
U.L. LISTED INSTRINSICALLY SAFE
FOR USE IN HAZARDOUS LOCATIONS
CLASS I, DIV. 1, GRPS. C & D;
CLASS II, DIV. 1, GRPS. E, F & G;
CLASS III, DIV. 1
APPROVED SEAL
IE: EXPLOSION PROOF
CONDUIT SEAL
CONDUIT
SHIELDED CABLE
(SEE CABLE NOTE)
SEALED JUNCTION BOX
G
_
+
CONTACT
CLOSURES
HAZARDOUS LOCATION
NON HAZARDOUS LOCATION
TO ADDITIONAL
PROBES
AS REQUIRED
WIRE IDENTICAL
AS ABOVE
TO ADDITIONAL
CONTACT
AS REQUIRED
WIRE IDENTICAL
AS ABOVE
WHITE
COM
COM
XIN1
XIN2
COM
COM
COM
NC
NC
NC
NC
NC
NO
NO
NO
NO
RELAY #4
RELAY #3
RELAY #2
RELAY #1
INSTRINSICALLY
SAFE PROBE
TERMINALS
OPTIONAL RELAY
CONTACT OUTPUTS
120 VAC MAX.
7.5 AMP MAX.
TO DOOR OF ENCLOSURE
DISPLAY CONNECTOR
PRINTER
CONNECTOR
INTRINSICALLY SAFE OUTPUTS
CONTACTS
PROBES
RS232
B CHANNEL
CONNECTOR
RS232
A CHANNEL
CONNECTOR
FOR WIRING
DETAILS
SEE DRW.
X76D474-1
FOR WIRING DETAILS
SEE DRW. X76D474-1
INSTRINSICALLY
SAFE CONTACT
TERMINALS
+
1
2
3
3
1
1
3
3
4
4
5
5
6
6
7
7
8
8
2
2
2
1
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
BLACK
LINE
NOISE
FILTER
120 VAC
0.4 AMP
60 Hz
GND
HI (H)
LO (N)
C
O
M
L
X
1
L
X
2
L
X
3
L
X
4
X76CTM-4X
TANK MONITOR
GROUNDING NOTES
CABLE NOTES
INTRINSICALLY SAFE TERMINAL NOTES
1. The resistance between the ground screw and the system
earth ground must be < 1 Ohm.
2. The transducer ground wire shall be connected to drain wire
or shield wire of cabling. Do not terminate drain wire at panel.
1. Probe terminals may only be connected to U.L. listed 950xxxB
model probes (xxx = probe length).
2. Contact terminals may only be connected to passive contacts.
3. Wiring shield cover must be installed securely in place prior to
applying operating power.
1. Cable sets that run together must be installed per ISA
Standard #RP126.
2. For transducer cable lengths up to 1000 ft., shielded cable
(#8441 Belden or equivalent) or heavier gauge can be used,
cable capacitance shall be < 60 pF per foot. Cable
inductance shall be < 0.2 H per foot.
m
3. For contact cable lengths up to 1000 ft., unshielded twisted
pair cables are recommended. Cable capacitance shall be
< 60 pF per foot. Cable inductance shall be < 0.2 H per foot.
4. For transducer and/or contact cable lengths exceeding 1000 ft.
and up to 2500 ft., twin axial Belden cable #9182 (U.L. 2606)
must be used.
m
X76CTM SYSTEM
WIRING INFORMATION
NOTE:
Reference Ronan Engineering
Drawing Number X76D515.
X76CTM
TANK MONITOR