Emergency manual release, Ds2 programming switches, Factory settings are shown in bold italic type – Controlled Products Systems Group PATRSL User Manual
Page 19: Emergency manual release cover

17
DS2 Programming Switches
Factory settings are shown in bold italic type
1 Solenoid lock enable / Gate in operation indicator
ON
Solenoid lock output energizes half second before gate begins to move and remains energized
until four seconds after reaching a limit (+12Vdc output 1.5 amp max)
OFF
Solenoid lock / gate in operation indicator is inactive
2 Magnetic lock enable
ON
Magnetic lock relay is active and will release half second before gate
begins to open (+12 vdc output 1.5 amp max)
OFF
Magnetic lock relay is inactive
3 Security Shunt Circuit Enable / Open Gate Indicator
ON
Security shunt circuit relay is active (closed circuit)(wire in parallel)
OFF
Security shunt circuit relay is inactive (open circuit)
4 Motion Detector Enable
ON
Activates motion detector input (if input is activated gate will not open)
OFF
Disables motion detector input
Emergency Manual Release
Emergency manual release cover
Remove lock and rotate emergency manual release cover to the up position.
Pull manual release knob out (about ¾ inch)
Once knob has been pulled the gate can then be pushed by hand.
If knob cannot be pulled the gate may need to be agitated left or right.
To reset the knob push in on knob and roll gate until knob snaps in place. It may be
necessary to tap the knob inward to fully lock in place.
WARNING: Only insert hand into access hole as far as needed to grip the
release
knob.
Trying to insert hand farther can result in injury
.
Siren Output
OPEN/CLOSE
COMMAND
Vehicular Gate Operator
Gate Weight Max. Load: 650 lbs.
LED INDICATOR
S2
RESET
Entrapment
S
E
C
U
R
I
T
Y
S
H
U
N
T
C
O
M
M
O
N
G
N
D
M
A
G
L
O
C
K
S
O
L
O
N
O
I
D
L
O
C
K
C
O
M
M
O
N
G
N
D
O
U
T
P
U
T
+
1
2
V
O
N
2
3
4
1
SOLONOID LOCK ENABLE
MAGNETIC LOCK ENABLE
SECURITY SHUNT ENABLE
MOTION DETECTOR ENABLE
15
5
0
10
TIMER TO CLOSE
ADJUSTMENT
Timer
ADJUSTMENT
Class I or Class II per UL325
J2
INDICATORS
1-
+12V OUT 1.5 AMP MAX
2- COMMON
GROUND
3-
PUSH BUTTON INPUT
4-
OPEN SAFETY EDGE
5- CLOSE
INPUT
6-
SECONDARY ENTRAPMENT DEVICE INPUT
7- COMMON
GROUND
8-
STOP CIRCUIT INPUT N/C
9-
FREE EXIT / OPEN INPUT
10-
UNDER GATE / CENTER LOOP INPUT
11-
SAFETY LOOP / REVERSING EDGE INPUT
12-
MOTION DETECTOR INPUT
1 2 3 4 5 6 7 8 9 10 11 12
J2
BOTH ON FOR DUAL
DS1 SWITCH SETTINGS
FACTORY SETTINGS
SW-1
AUTO CLOSE TIMER ENABLE
OFF
SW-2
TIMER TO CLOSE WILL ACTIVATE ON LIMIT ONLY
ON
SW-3
MASTER GATE ENABLE
ON
SW-4
SLAVE GATE ENABLE
OFF
SW-5
SOLENOID LOCK OPTION, SEE INSTALLATION MANUAL
OFF
SW-6
SOFT STOP RETRACT ENABLE
OFF
SW-7
SOFT STOP EXTEND ENABLE
OFF
SW-8
STOP CIRCUIT ENABLE
OFF
SW-9
OPERATING DIRECTION REVERSE
OFF
SW-10
SOFT START ENABLE FOR SW6 AND SW7
OFF
1
2
3
4
5
6
7
8
9
10
O
N
DS1
PATRIOT CONTROL BOARD
USAutomatic
MADE IN USA
CURRENT SENSE
ADJUSTMENT
0
10
5
MASTER
Sensitivity
CURRENT SENSE
ADJUSTMENT
0
10
5
SLAVE
Sensitivity
15