beautypg.com

Troubleshooting – GF Signet 8450 Pressure Transmitter User Manual

Page 8

background image

Troubleshooting

Georg Fischer Signet LLC, 3401 Aero Jet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057
For Worldwide Sales and Service, visit our website: www.gfsignet.com • or call (in the U.S.): (800) 854-4090
For the most up-to-date information, please refer to our website at www.gfsignet.com

3-8450.090-3 Rev. J 01/13 English

© George Fischer Signet, Inc. 2013

Ordering Information

Mfr. Part No.

Code

Description

3-8450-1

159 000 041

Pressure transmitter, Field mount

3-8450-1P

159 000 042

Pressure transmitter, Panel mount

3-8450-2

159 000 043

Pressure transmitter, Field mount with relays

3-8450-2P

159 000 044

Pressure transmitter, Panel mount with relays

3-8450-3

159 000 045

Pressure transmitter, Field mount with dual input/output

3-8450-3P

159 000 046

Pressure transmitter, Panel mount with dual input/output

Accessories

Mfr. Part No.

Code

Description

3-8050

159 000 184

Universal mounting kit

3-8052

159 000 188

3/4 in. Integral mounting kit

3-8052-1

159 000 755

3/4 in. NPT mount junction box

3-8050.395

159 000 186

Splashproof rear cover

3-8050.396

159 000 617

RC Filter kit (for relay use)

3-0000.596

159 000 641

Heavy duty wall mount bracket

3-5000.598

198 840 225

Surface Mount Bracket

3-9000.392

159 000 368

Liquid tight connector kit for rear cover (includes 3 connectors)

3-9000.392-1

159 000 839

Liquid tight connector kit, NPT (1 piece)

3-9000.392-2

159 000 841

Liquid tight connector kit, PG13.5 (1 piece)

Display Condition

Possible Causes

Suggested Solutions

Check Sensor?

• Sensor not wired properly.
• Sensor connected to 8450 while

power is on.

• Defective

sensor.

• Correct sensor wiring.
• Recycle power with all sensors connected.
• Replace defective sensor.

Too much error

CHECK SENSOR

The value entered in Set Pressure fi eld is
greater than 5 psi deviation from sensor
input. (The 8450 allows a maximum of
5 psi calibration offset.).

• Confi rm calibration values.
• Remove sensor from installation, check

8450 reading (should be zero). If necessary,
Set Pressure to zero, reinstall sensor, then
recalibrate.

Reset to Factory

Calibration

Value in SET PRESSURE fi eld is -999.

Entering "-999" in this fi eld will remove all user
calibration input and restore the factory values.

Relay is always activated

• Hysteresis value too large
• Defective

transmitter

• Change the hysteresis value
• Replace

transmitter

SETUP READ ERROR

Press Any Key

Memory fault occurred.

• Press any key to reload factory presets.
• Reprogram all setpoints.
• If this message appears again, replace the

8450.