Current output i2 0/4 to 20 ma – Fluid Components International CMB User Manual
Page 83
This function allows the operator to define the measured value to be output as an analog signal via cur-
rent output I1. When devices with HART
®
communication capabilities are used, current output I1 is usu-
ally assigned to mass flow. Press
↵ to display the current setting.
I1 assigned to
[Mass flow]
As mentioned in Section 12.4.3.1 Selection window/make a selection, the operator can choose between
the following settings:
¾
Mass
flow
¾
Volume
flow
¾
Density
¾
Temperature
13.10.4 Current output I2 0/4 to 20 mA
The Current output I2 0/4 to 20 mA function allows the operator to define the range in which the current
output is to be operated. The range from 4 to 20.5 mA follows the NAMUR recommendation and covers
the range from 0 to 104 % of the measuring range. The standard range from 4 to 21.6 mA allows for a
control of the measuring range of up to 110 %.
Press
↵ to display the current setting.
Current output I2
[4] – 21.6 mA
As mentioned in Section 12.4.3.1 Selection window/make a selection, the operator can choose between
the following settings:
CMB & CT OPERATING MANUAL
Part No 06EN003384 rev. 1.6
Page 83 of 106