This function allows the operator to define the measured value to be output as an analog signal via cur-
rent output I1. When devices with HART

®

communication capabilities are used, current output I1 is usu-

ally assigned to mass flow. Press

↵ to display the current setting.

I1 assigned to

[Mass flow]


As mentioned in Section 12.4.3.1 Selection window/make a selection, the operator can choose between
the following settings:

¾

Mass

flow

¾

Volume

flow

¾

Density

¾

Temperature


13.10.4 Current output I2 0/4 to 20 mA



The Current output I2 0/4 to 20 mA function allows the operator to define the range in which the current
output is to be operated. The range from 4 to 20.5 mA follows the NAMUR recommendation and covers
the range from 0 to 104 % of the measuring range. The standard range from 4 to 21.6 mA allows for a
control of the measuring range of up to 110 %.

Press

↵ to display the current setting.

Current output I2

[4] – 21.6 mA


As mentioned in Section 12.4.3.1 Selection window/make a selection, the operator can choose between
the following settings: