beautypg.com

Mass flow qm unit, Mass flow qm range – Fluid Components International CMB User Manual

Page 63

background image

13.5.1 Mass flow QM unit


Using this function, the operator can define the physical unit for all display functions, limit values and the
upper-range value of mass flow. After choosing the Mass flow QM unit function and pressing

↵, the fol-

lowing selection field will be displayed:

Mass flow QM unit

[kg/h]


According to the description in Section 12.4.3.1 Selection window/make a selection, one of the following
units can be selected:

¾

kg/s, kg/min, kg/h

¾

t/h

¾

g/min

¾

lbs/s, lbs/min, lbs/h

¾

shton/h

¾

lton/h

Press

↵ to confirm and save the selection.


13.5.2 Mass flow QM range


This function allows the operator to set the upper-range value for mass flow. The upper-range value
takes on the unit defined using the Mass flow unit function. The upper-range value will scale the current
and frequency outputs assigned to mass flow. After choosing the Mass flow QM range function and
pressing

↵, the following selection field will be displayed:

QM range=100%

XXXXX.XX kg/h


The current upper-range value for mass flow will be displayed. According to the description in Section
12.4.3.2 Input window/modify a value, the current value can be changed.

CMB & CT OPERATING MANUAL
Part No 06EN003384 rev. 1.6

Page 63 of 106