6 technical data, 6technical data – Burkert Type 8025 User Manual
Page 7

7
Technical data
Type 8025 UNIVERSAL
6
TEchNIcAL DATA
6.1
conditions of use
Ambient▶temperature
-10▶to▶+60▶°C
Air▶humidity
<▶80▶%,▶non▶condensated
Height▶above▶sea▶level
max.▶2000▶m
Installation▶class
Class▶I▶acc.▶to▶UL▶61010-1
Degree▶of▶pollution
Degree▶2▶acc.▶to▶EN▶61010-1
Protection▶rating
•▶ wall-mounted▶version▶
▶
▶
▶
•▶ panel▶version
acc.▶to▶EN▶60529
•▶ IP65,▶device▶wired,▶cable▶glands▶
tightened,▶cover▶lid▶screwed▶tight▶and▶
entry▶item▶nuts▶of▶the▶cable▶glands▶
tightened▶at▶a▶screwing▶torque▶of▶
1.5▶Nm.
•▶ front▶side▶IP65,▶rear▶side▶IP20
6.2
conformity to standards and
directives
The▶device▶conforms▶to▶the▶EC▶directives▶through▶the▶following▶
standards:
•▶ EMC:▶EN▶61000-6-2,▶EN▶61000-6-3
•▶ LVD:▶EN▶61010-1
•▶ Environnemental▶testing:
▶
- Vibration:▶EN▶60068-2-6,
▶
- Shock:▶EN▶60068-2-27.
The▶UL▶devices▶with▶PU01▶variable▶key▶comply▶with▶the▶following▶
standards:
•▶ UL▶61010-1
•▶ CAN/CSA-C22.2▶n°▶61010-1
6.3
mechanical data
part
material
Housing▶and▶cover,▶wall-mounted▶version
ABS
Cable▶glands,▶wall-mounted▶version
PA
Open▶housing,▶panel▶version
PC
Foil
polyester
4▶screws
Stainless▶steel
Cable▶clips
PA
English