Remedy

Check the electrical
connection

Ensure the operational
voltage agrees with that on
the nameplate

Lay out the pressure supply
with as large a volume as
possible (including upstream
devices such as pressure
regulators, service units,
shut-off valves etc.)
Minimum operating
pressure

≥≥≥≥≥ 2,5 bar

Lay out the pressure supply
with as large a volume as
possible (including upstream
devices such as pressure
regulators, service units,
shut-off valves etc.)
Minimum operating
pressure

≥≥≥≥≥ 2,5 bar

Use silencers or expansions
vessels of the corresponding
size

Clean out the soiled silencers

Apply pressure surges to the
discharged air channels to
blow out the soiling; Install a
new pilot or main valve if this
measure is unsuccessful.

7

FAULTS

Possible cause

No operational voltage, or
voltage insufficient

Pressure supply insufficient,
or not present

Pressure supply insufficient,
or not present

Insufficient air venting of the
discharged air channel due
to silencers that are too
small or are soiled (back-
pressure)

Soiling or foreign bodies in
the pilot or main valve

Fault

Valve does not
switch

:

Valve switches after a
delay, or blows out of
the air vent ports: